Data Sheet for Product

4/6
Siemens Air damper actuators for lab applications GNP19.. CE1N4609en
Smart Infrastructure 2021-12-03
Technical data
Operating voltage / Frequency
Power consumption: Actuator running
Hold
AC/DC 24 V 20 % / 50/60 Hz
20 VA / 13 W
5 W
Nominal torque
Maximum torque (when blocked)
Nominal rotary angle / max. rotary angle
Runtime for 90° rotary angle
6 Nm
18 Nm
90° / max. 95°
2 s (50 Hz)
Input voltage Y/Y1+ (wires 8-2)
Positioning resolution for DC 0 (2)...10 V / 0 (4)…20 mA
Max. permissible input voltage
DC 0 (2)...10 V / 0 (4)…20 mA or
AC/DC 0 V , AC/DC 24 V "open“
250 steps for 90 °
AC/DC 24 V 20 %
Input voltage Y2+ (wires 7-2)
Max. permissible input voltage
AC/DC 0 V , AC/DC 24 V "close“
AC/DC 24 V 20 %
Output voltage U (wires 9-2)
max. output current
DC 0 (2)...10 V
DC 1 mA
Contact loading
Voltage (no mixed operation 24 VAC / 230 VAC)
Switching range for auxiliary switches
Setting increments
6 A resistive, 2 A inductive
AC 24...230 V
5°...90°
Cross-section
Standard length
0.75 mm
2
0.9 m
Protection class as per EN 60 529 (observe mounting notes) IP 54
Insulation class
230 VAC, auxiliary switch
EN 60 730
ll
Operation / Transport
Temperature
Humidity (non-condensing)
IEC 721-3-3 / IEC 721-3-2
18...50 °C / 32...70 °C
< 95% r.h. / < 95% r.h.
Product safety: Automatic electronic controls for household and
similar use
EN 60 730-2-14
(Type 1)
Electromagnetic compatibility (Application) For residential, commercial and
industrial environments
EU Conformity (CE) A5W00004382
1)
RCM Conformity A5W00004383
1)
Product environmental declaration
2)
CE1E4608en
1)
Actuator W x H x D (see Dimensions)
Damper shaft: Round
Square
Min. shaft length
81 x 192 x 63 mm
6.4…20.5 mm
6.4…13 mm
20 mm
Excl. packaging 1.230 kg
1)
The documents can be downloaded from http://siemens.com/bt/download
2)
The product environmental declarations contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition, packaging, environmental benefit,
disposal).
24 VAC/VDC supply
(SELV/PELV)
Functional data
Positioning signal Y/Y1
Positioning signal Y2
Position indicator
Auxiliary switch
for GNP196.1E
Connection cable
Housing type
Protection class
Environmental conditions
Standards, guidelines
Dimensions
Weight