Installation Instructions
Document No. 129-402
Installation Instructions
June 6, 2018
Siemens Industry, Inc. Page 3 of 5
Wiring Diagrams
NOTE: All wiring must conform to NEC and local codes and regulations.
24 Vac/dc
Function Color
Supply Red
Neutral Black
Ground Green
120 Vac
Function Color
Line Black
Neutral White
Ground Green
230 Vac
CAUTION:
The actuator must be wired
with a 230 Vac line with
respect to neutral. The
ground lead must be
connected for proper
protection of the actuator.
Any other connection, such
as phase-to-phase, can
damage the actuator.
Function Color
Line Brown
Neutral Blue
Ground Green
Fixed Dual
End Switches
Switch
Wire
Color
Switch
Makes
Switch
Breaks
5° Gray < 5° > 5°
85° Yellow > 85° < 85°
NOTE:
Both sets of contacts are open when actuator
is between 5° and 85°.
CAUTION:
Mixed switch operation to the switching outputs
of both dual end switches (5° and 85°) is not
permitted.
Either AC line voltage from the same phase
must be applied to all four outputs of the fixed
dual end switches, or UL-Class 2 voltage must
be applied to all four outputs.