Data Sheet for Product

Table Of Contents
3/6
Siemens Air damper actuators GMA...1, rotary version with spring return CM2N4614en
Smart Infrastructure 2021-09-08
Safety
Caution
National safety regulations
Failure to comply with national safety regulations may result in personal injury and
property damage.
Observe national provisions and comply with the appropriate safety regulations.
Use only properly trained technicians for mounting, commissioning, and servicing.
Technical data
Operating voltage
AC / Frequency
Operating voltage (DC)
Power consumption
GMA1..1: Running
GMA12..1, 13..1: Holding
GMA16..1,: Holding
AC 24 V
± 20 % / 50/60 Hz
DC 24…48 V
±20 %
AC: 5 VA / 3.5 W // DC: 3.5 W
AC/DC: 2 W
AC/DC: 2.5 W
Operating v
oltage / Frequency
Power consumption
GMA32..1: Running
Holding
AC 230 V
± 10 % / 50/ 60 Hz
7 VA / 4.5 W
3.5 W
Nominal torque
Maximum torque (blocked)
Nominal rotary angle / Max. rotary angle
Runtime for rot
ary angle 90° (motor operation)
Closing time with return spring (on power failure)
7 Nm
21 Nm
90° / 95°
±
90 s
15 s
Switching current (at AC 24 V / DC 24…48 V)
for "Open"/"Close" (cores 6,7)
normally 8 mA
Input voltage Y (wires 8
-2)
Max. permissible input voltage
DC 0...10 V / DC 2...10 V
DC 35 V
Input voltage Y (wires 8
-2)
Non-adjustable characteristic function
Adjustable characteristic function
Offset Uo
Span U
DC 0...35 V
DC 0...10 V / DC 2...10 V
DC 0...5 V
DC 2...30 V
Output voltage U (cores 9
-2)
Max. output current
DC 0...10 V
DC ± 1 mA
Ch
ange of resistance (wires P1-P2)
Load
0...1000
< 1 W
AC 24 V
DC 24…48 V supply
(SELV/PELV)
AC 230 V supply
Function data
Positioning signal for GMA13..1
Positioning signal for GMA16..1
Characteristic functions
for GMA161.1, 166.1
for GMA163.1, 164.1
Position indicator for GMA16..1
Feedback potentiometer
for GMA132.1