Data Sheet for Product
Table Of Contents
- Functions
- Type summary
- Ordering (Example)
- Equipment combinations
- Product documentation
- Notes
- Safety
- Mounting
- Mounting positions
- Commissioning
- Maintenance
- Disposal
- Warranty
- HMI (Human-Machine Interface)
- Push-button operation
- LED colors and patterns
- Resetting the device by push button
- Push-button addressing
- Display current address (starting with lowest address digit)
- Set new address (starting with lowest address digit)
- Examples
- Modbus registers
- Register 769 “Status”
- Supported function codes
- Technical data
- Diagrams
- Internal diagrams
- Note
- Dimensions
8 / 14
Siemens A6V101037201_en--_b
Smart Infrastructure 2021-09-07
Examples
Set address “124”:
1. Enter addressing mode
2. Set 1-digits: Press button 4-times LED flashes red per button press
3. Store 1-digits: press button until LED shines green – release button
4. Set 10-digits: Press button 2-times LED flashes green per button press
5. Store 10-digits: press button until LED shines orange – release button
6. Set 100-digits: Press button 1-times LED flashes orange per button press
7. Store address: press button until LED shines red – release button
address is stored and displayed 1x for confirmation
Set address “50”:
1. Enter addressing mode
2. Skip 1-digits: Hold button pressed until LED shines green – release button
3. Set 10-digits: Press button 5-times LED flashes green per button press
4. Store address (skip 100-digits): hold button pressed until LED shines red
– release button
address is stored and displayed 1x for confirmation
Set address “5”:
1. Enter addressing mode
2. Set 1-digits: Press button 5-times LED flashes green per button press
3. Store address: press button until LED shines red
address is stored and displayed 1x for confirmation