Data Sheet for Product
Table Of Contents
- Functions
- Type summary
- Ordering (Example)
- Equipment combinations
- Product documentation
- Notes
- Safety
- Mounting
- Mounting positions
- Commissioning
- Maintenance
- Disposal
- Warranty
- HMI (Human-Machine Interface)
- Push-button operation
- LED colors and patterns
- Resetting the device by push button
- Push-button addressing
- Display current address (starting with lowest address digit)
- Set new address (starting with lowest address digit)
- Examples
- Modbus registers
- Register 769 “Status”
- Supported function codes
- Technical data
- Diagrams
- Internal diagrams
- Note
- Dimensions
6 / 14
Siemens A6V101037201_en--_b
Smart Infrastructure 2021-09-07
HMI (Human-Machine Interface)
Push-button operation
Activity Push-button operation Confirmation
Display current address
(starting with lowest address digit)
Press button < 1s 1-digits: red
10-digits: green
100-digits: orange
If termination is switched on, LED
flashes 1x blue after address display
Example:
124 = 4x red, 2x green, 1x orange
Turn bus termination on / off
turn on
1. press 3x
LED flashing and flickering stops
(termination mode)
2. press 1x shortly LED flashes 1x blue
3. press button until LED shines red LED shines red (confirmation)
4. release button LED off
Address display
LED flashes 1x blue after address
display
Normal operation
turn off
1. press 3x
LED flashing and flickering stops
(termination mode)
2. press button until LED shines red LED shines red (confirmation)
3. release button Normal operation
Enter Modbus address with push-
button
Press button > 1s and < 5s
See chapter ‘Push-button addressing’
below
Enter push-button addressing
mode
(for use with Climatix
TM
controllers)
1. Press button > 5s and < 10s
2. Release button
LED shines red and gets dark after 5s
LED shines orange
Reset to factory settings Press button > 10s LED flashes orange