Data Sheet for Product

12 / 14
Siemens A6V101037201_en--_b
Smart Infrastructure 2021-09-07
Diagrams
Internal diagrams
The damper actuators are supplied with a prewired connecting and communication cable. All
interconnected devices must be connected to the same G0.
Core desig. Core color Terminal code Description
1 red (RD) G System potential AC 24 V ~ / DC 24 V
2 black (BK) G0 System neutral
6 violet (VT) REF Reference (Modbus RTU)
8 grey (GY) + Bus + (Modbus RTU)
9 pink (PK) - Bus - (Modbus RTU)
Note
The operating voltage at terminals G and G0 must comply with the requirements under
SELV or PELV. Safety transformers with twofold insulation as per EN 61558 required; they
must be designed to be on 100 % of the time.