Power GMA1..9E..
Operating voltage AC
AC 24 V ± 20 %
Frequency
50/60 Hz
Operating voltage DC
DC 24…48 V ± 20 %
Power consumption
Operation
AC: 5 VA / 3.5 W
DC: 3.5 W
Hold
GMA121.9E / GMA131.9E
AC / DC: 2 W
GMA161.9E..
AC / DC: 2,5 W
Power GMA321.9E
Operating voltage
AC 230 V ± 10 %
Frequency
50/60 Hz
Power consumption
Operation
7 VA / 4.5 W
Hold
3.5 W
Function data
Nominal torque
7 Nm
Maximum torque (when blocked)
21 Nm
Minimum holding torque
4 Nm
Nominal rotation angle (with position indication)
90°
Maximum rotation angle (mechanically limited)
95° ± 2°
Runtime at nominal rotational angle 90°
90 [s]
Closing time with spring return (on power failure)
15 s
Inputs GMA1..9E..
Positioning signal
Switching current (at AC 24 V / DC 24…48 V =)
for "Open"/"Close"
> AC / DC 8 mA
Input voltage Y
(wires 8-2)
DC 0…10 V =
Max. permissible input voltage
DC 35 V
(Wires 9-2)
DC 0…10 V =
Max. output current
DC ± 1 mA