User Manual

4/6
Siemens Rotary actuators for ball valves GMA..9E CM2N4658en
Smart Infrastructure 2019-09-26
When commissioning the system, check wiring and the function of the rotary actuator.
Technical data GMA..9E
Operating voltage AC / Frequency
Operating voltage (DC)
Power consumption GMA1.1.9E: Running
GMA121.9E/GMA131.9E: Holding
GMA161.9E: Holding
AC 24 V ± 20 % / 50/60 Hz
DC 24…48 V ±20 %
AC: 5 VA / 3.5 W // DC: 3.5 W
AC/DC: 2 W
AC/DC: 2.5 W
Operating voltage AC / Frequency
Power consumption GMA321.9E Running
Holding
AC 230 V ± 10 % / 50/60 Hz
7 VA / 4.5 W
3.5 W
Nominal torque
Nominal rotary angle / Max. rotary angle
Runtime for rotary angle 90° (motor operation)
Closing time with return spring (on power failure)
7 Nm
90° / 95° ±
90 s
15 s
Switching current (at AC 24 V / DC 24…48 V)
for "Open"/"Close"
> AC/DC 8 mA
Input voltage Y (wires 8-2)
Max. permissible input voltage
DC 0...10 V
DC 35 V
Output voltage U (wires 9-2)
Max. output current
DC 0...10 V
DC ± 1 mA
Cross-section of the prewired connection cables
Standard length
0.75 mm
2
0.9 m
Degree of protection as per EN 60 529
(note mounting instructions)
IP54
Insulation class
AC 24 V / DC 24…48 V
AC 230 V
EN 60730
lll
ll
Operation / Transport
Climatic Conditions
Temperature
Humidity (non-condensing)
IEC 60721-3-3 / IEC 60721-3-2
Class 3K5 / Class 2K3
-32...+55 °C / -32...+70 °C
< 95% r. h. / < 95% r. h.
Product standards
Automatic electrical controls for
household and similar use
EN 60730-2-14
(Mode of operation, Type 1)
Electromagnetic compatibility
(Application)
For residential, commercial and
industrial environments
EU Conformity (CE)
8000081792
1)
RCM Conformity
8000081793
1)
Product environmental declaration
2)
CE1E4614en
1)
Without packaging: GMA1..9E
GMA3..9E
1.2 kg
1.3 kg
1)
The documents can be downloaded from http://siemens.com/bt/download
2)
The product environmental declaration contains data on environmentally compatible product design
and assessments (RoHS compliance, materials composition, packaging, environmental benefit, dispos-
al).
Orientation
Commissioning
Supply voltage
AC 24 V
DC 24…48 V
(SELV / PELV)
Supply voltage
AC 230 V
Function data
Positioning signal
for GMA131.9E
Positioning signal
for
GMA161.9E
Position indicator
for GMA161.9E
Connection cables
Degree of protection of
housing
Protection class
Environmental conditions
Standards and directives
Weight