s OpenAir™ Air damper actuators GLB..1E Electronic motor driven actuators for open-close, three-position and modulating control ● ● ● ● ● Nominal torque 10 Nm Operating voltage AC 24 V ~ / DC 24…48 V ⎓ or AC 100…240 V ~ Mechanically adjustable span between 0...90° Pre-wired with 0.
Use The rotary actuators are used in ventilation and air conditioning plants to regulate and shut off air dampers: ● For damper areas up to 1.6 m2 (guideline, always observe damper manufacturer’s data). ● Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position controllers for air dampers or air throttles. ● We recommend a minimum pulse length of 500 ms on rotary actuators operated with 3point control to ensure continuous and accurate operation.
Actuator motor / Gears ● Brushless, robust DC motors ensure reliable operation regardless of load. The damper actuators do not require an end position switch, are overload proof, and remain in place upon reaching the end stop. ● The gears are maintenance free and low noise. Type summary Type Stock no. Control Operating voltage Openclose or threeposition AC 24 V ~ / Positioning signal Y Position indicator U = DC 0…10 V ⎓ GLB146.1E S55499-D387 GLB341.1E S55499-D388 GLB346.
Engineering Potentiometer and auxiliary switches Potentiometer and auxiliary switches cannot be added in the field. Installation WARNING No internal line protection for supply lines to external consumers Risk of fire and injury due to short-circuits ● Adapt the line diameters as per local regulations to the rated value of the installed fuse. Maintenance The actuators GLB..1E are maintenance-free.
Inputs Positioning signal for GLB14..1E Operating voltage AC/DC 24 V AC 24 V ~ / DC 24…48 V ⎓ (wires 1-6/G-Y1) (wires 1-7/G-Y2) clockwise counterclockwise Positioning signal for GLB34..1E Operating voltage AC 100…240 V ~ (wires 4-6/N-Y1) (wires 4-7/N-Y2) clockwise counterclockwise (wires 8-2/Y-G0) DC 0/2…10 V ⎓ 0.1 mA >100 kW Positioning signal for GLB16..1.E Input voltage Current consumption Input resistance Max.
Environmental conditions Operation Climatic conditions Mounting location Temperature extended Humidity (non-condensing) IEC 60721-3-3 Class 3K5 interior, weather-protected -32…+55 °C <95 % r.F. Transport Climatic conditions Temperature extended Humidity (non-condensing) IEC 60721-3-2 Class 2K3 -32…+70 °C <95 % r.F. Storage Climatic conditions Temperature extended Humidity (non-condensing) IEC 60721-3-1 Class 1K3 -32…+50 °C <95 % r.F.
Diagrams Internal Diagrams GLB14..1E GLB34..1E (open-close, three-p.) AC 24 V ~ / DC 24…48 V ⎓ (open-close, three-p.) AC 100…240 V ~ GLB16..1E (modulating, Y= DC 0/2…10 V ⎓) GLB16..1E (modulating, Y= DC 0…35 V ⎓) AC 24 V ~ / DC 24…48 V ⎓ AC 24 V ~ / DC 24…48 V ⎓ GLB361.1E (modulating control) AC 100…240 V ~ Connection diagrams GLB1..
GLB3.. 1E (AC 100…240 V ~) Open-close, single wire control Open-close, two wire control Single Pole Single Throw (SPST) Single Pole Double Throw (SPDT) Three-position control Modulating control Cable labeling Connection Code No Color Abbreviation Meaning Actuators G 1 red RD System potential AC 24 V ~ / DC 24…48 V ⎓ AC 24 V ~ G0 2 black BK System neutral DC 24…48 V ⎓ Y1 Y2 6 7 purple orange VT OG Positioning signal AC/DC 0 V, “clockwise” (GLB14..
2.7 Dimensions x 68 min. 60 min. 4634M01 min. 6 50 max 95° 4.5 Dimensions in mm Revision numbers Type Valid from rev. no. Type Valid from rev. no. GLB141.1E ..C GLB164.1E ..A GLB142.1E ..C GLB166.1E ..C GLB146.1E ..C GLB361.1E ..C GLB161.1E ..C GLB341.1E ..C GLB163.1E ..A GLB346.1E ..
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel. +41 41-724 24 24 www.siemens.com/buildingtechnologies Document ID A6V10636202_enAP_c Issue 2018-01-25 © Siemens Switzerland Ltd, 2016-2018 Technical specifications and availability subject to change without notice.