Data Sheet for Product

8 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
Technical data
Power supply (GLB1..9E..)
Operating voltage (SELV/PELV) /
Frequency
GLB141.9E
GLB161.9E
AC 24 V ~ ±20 % (19,2…28,8 V ~) / 50/60 Hz
DC 24…48 V
±20 % (19,2…57,6 V
)
1)
GLB161.9E/MO AC 24 V ~ ±20 % (19,2…28,8 V ~) / 50/60 Hz
DC 24 V
±20 % (19,2…28,8 V
)
Power consumption running GLB141.9E
GLB161.9E
GLB161.9E/MO
2.2 VA / 1.3 W
2.5 VA / 1.5 W
3.0 VA / 2.0 W
Power consumption holding GLB141.9E
GLB161.9E
GLB161.9E/MO
0.5 W
0.7 W
1.2 W
Power supply (GLB341.9E)
Operating voltage / Frequency AC 100…240 V ~ ±10 %; 50 / 60 Hz
Power consumption running
Power consumption holding
6 VA / 2 W
0.9W
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
10 Nm
16 Nm
10 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ±
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
Inputs
Positioning signal for GLB141.9E
Operating voltage
AC 24 V ~ / DC 24…48 V
(wires 1-6/G-Y1)
(wires 1-7/G-Y2)
clockwise
counterclockwise
Positioning signal for GLB341.9E
Operating voltage
AC 100…240 V ~
(wires 4-6/N-Y1)
(wires 4-7/N-Y2)
clockwise
counterclockwise
Positioning signal for GLB161.9E..
Input voltage
Current consumption
Input resistance
(wires 8-2/Y-G0)
DC 0/2…10 V
0.1 mA
>100 k
Max. permissible input voltage
Protected against faulty wiring
Hysteresis
DC 35 V
limited to DC 10 V
max. AC 24 V ~
60 mV
Communication GLB161.9E/MO
Communication protocol
Modbus RTU RS-485, not galvanically isolated
Number of nodes Max. 32
Address range 1...248 / 255
Factory setting 255
Transmission formats 1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Factory setting 1-8-E-1
Baud rates (kbaud) Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2
Factory setting Auto
Bus termination 120 Ω electronically switchable
Factory setting Off