Data Sheet for Product
2 / 14
Siemens A6V10636203_en--_f
Smart Infrastructure 2021-11-08
Features
● Brushless, robust DC motors ensure reliable operation regardless of load.
● The rotary actuators do not require an end position switch, are overload proof, and remain
in place upon reaching the end stop.
● The gears are maintenance free and low noise.
● Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position
controllers.
● We recommend a minimum pulse length of 500 ms on rotary actuators operated with 3-
point control to ensure continuous and accurate operation.
Functions
GLB..
AC 24 V ~ /
DC 24…48 V
⎓
141.9E 161.9E ─
AC 24 V ~ /
DC 24 V
⎓
─ ─ 161.9E/MO
AC 100…240 V ~ 341.9E ─ ─
Control type Open-close / three-position Modulating control (0/2…10 V) Modbus RTU
Rotary direction Clockwise or counter-clockwise direction depends … ─
… on the type of control
… on the setting of the rotary
direction DIL switch.
With no power applied, the
actuator remains in the
respective position.
… on the setting of the rotary
direction DIL switch
… on the positioning signal.
The actuator remains in the
achieved position:
… if the control signal is
maintained at a constant value
… for loss of operating voltage.
─
NC (normally closed) ball valve NC (normally closed) ball valve ─
Signal on Y1
– rotation counter-clockwise
– ball valve opens
Signal on Y2
– rotation clockwise
– ball valve closes
DIL 2 set to “counter-clockwise”
(ccw)
Flow = 0% at Y = 0 V
Flow = 100% at Y = 10 V
─
NO (normally open) ball valve NO (normally open) ball valve ─
Signal an Y2
– rotation clockwise
– ball valve closes
Signal on Y1
– rotation counter-clockwise
– ball valve opens
DIL 2 set to “clockwise” (cw)
Flow = 100% at Y = 0 V
Flow = 0% at Y = 10 V
─
cw
ccw
G
D
.
.
1
E
_
Z
0
6
G
D
.
.
1
E
R
W
_
Z
0
8
cw
ccw
0
0...
2...
0
0...
2...