Data Sheet for Product

6 / 10
Siemens A6V10636203_enAP_d
Building Technologies 2018-01-25
Disposal
The device is considered an electronics device for disposal in terms of Eu-
ropean Directive 2012/19/EU and may not be disposed of as domestic gar-
bage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations..
Technical data
Power supply (GLB1..9E)
Operating voltage (SELV/PELV) / Frequency AC 24 V ~ ±20 % (19,2…28,8 V ~) / 50/60 Hz
DC 24…48 V ±20 % (19,2…57,6 V )
1)
Power consumption running GLB141.9E,
GLB161.9E
2.2 VA / 1.3 W
2.5 VA / 1.5 W
Power consumption holding GLB141.9E,
GLB161.9E
0.5 W
0.7 W
Power supply (GLB341.9E)
Operating voltage / Frequency AC 100…240 V ~ ±10 %; 50 / 60 Hz
Power consumption running
Power consumption holding
6 VA / 2 W
0.9W
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
10 Nm
16 Nm
10 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ±
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
Inputs
Positioning signal for GLB141.9E
Operating voltage
AC 24 V ~ / DC 24…48 V
(wires 1-6/G-Y1)
(wires 1-7/G-Y2)
clockwise
counterclockwise
Positioning signal for GLB341.9E
Operating voltage
AC 100…240 V ~
(wires 4-6/N-Y1)
(wires 4-7/N-Y2)
clockwise
counterclockwise
Positioning signal for GLB161.9E
Input voltage
Current consumption
Input resistance
(wires 8-2/Y-G0)
DC 0/2…10 V
0.1 mA
>100 kW
Max. permissible input voltage
Protected against faulty wiring
Hysteresis
DC 35 V limited to DC 10 V
max. AC 24 V ~
60 mV
Outputs
Position indicator (GLB161.9E)
Output signal
Output voltage U
Max. output current
(wires 9-2/U-G0)
DC 0...10 V
DC ±1 mA
Protected against faulty wiring max. AC 24 V ~ / DC 24…48 V