Data Sheet for Product
2/6 
Siemens  Air damper actuators GDB.../GLB..., Linear version  CM2N4664E 
Smart Infrastructure    2020-01-22 
Use 
• For damper areas up to 0.8 m
2 
(GDB) / 1.5 m
2
 (GLB), friction-dependent. 
• Suitable for modulating controllers (DC 0...10 V) or three-position controllers (e.g. 
rotary and linear dampers at air outlets). 
Type summary 
GDB.../GLB... 
131.2E 
136.2E 
331.2E 
336.2E 
1)
161.2E 
163.2E 
Control type 
Three-position control 
Modulating control 
Operating voltage 
AC 24 V 
X 
X 
X 
X 
Operating voltage 
AC 230 V 
X 
X 
Positioning signal Y 
DC 0...10 V 
X 
DC 0...35 V with character-
istic function Uo, U 
X 
Position indicator 
U = DC 0...10 V 
X 
X 
Self-adaptation of linear span 
X 
X 
Auxiliary switches (two) 
X 
X 
Linear direction switch 
X 
X 
1)
 While stocks last 
Functions 
Type 
GDB.3..2 / GLB.3..2 
GDB16..2 / GLB16..2 
Control type 
Three-position control 
Modulating control 
Positioning signal with ad-
justable characteristic func-
tion 
DC 0...35 V at 
Offset  Uo = 0...5 V 
Span  U = 2...30 V 
Linear travel direction 
The direction of linear travel depends on... 
…the type of control. With no power ap-
plied, the actuator remains in the respec-
tive position. 
...the DIL switch setting outward / inward.  
Position indication 
Position indicator: Output voltage  
U = DC 0...10 V is generated proportional 
to the linear travel. U depends of DIL 
switch setting. 
Auxiliary switch 
The switching points for auxiliary switches A and B can be set independent of each 
other in increments of 3.4 between 3.4 and 57.1 mm. 
Self-adaptation of linear 
span 
When self-adaptation is active, the actua-
tor automatically determines the mechani-
cal end positions of the linear span and 
maps the characteristic function (Uo, U) 
to the calculated linear span. 
Linear limitation 
Stepless limitation between 0 and 60 mm for the linear travel is possible  
by means of a clamp from the linear/rotary set ASK55.2 