Data Sheet for Product
3 / 14
A6V10631832_en--_f Siemens
2021-10-20 Smart Infrastructure
Product documentation
Title
Topic
Document ID
VAV Compact Controllers Modbus
RTU
Detailed information about the VAV Compact
Controllers with Modbus communication
A6V10631862
Installation Instruction VAV
Modbus / BACnet
Mounting / installation instruction
A6V10523083
How to obtain documentation and product-related software
Related documents such as environmental declarations, CE declarations, etc., can be down-
loaded at the following Internet address:
http://siemens.com/bt/download
HMI (Human-machine interface)
For more detailed explanations on device states, functions and error display, cf. product doc-
umentation A6V10631862
Push-button operation
Activity
Push-button operation
Confirmation
Display current address
(in reverse order)
Press button < 1s
Current address is displayed
Enter push-button addressing
mode
Press button > 1s and < 5s
Red LED shines (release button
before LED gets dark)
Reset to OEM default settings
Press button > 10s
Orange LED flashes
LED colors and patterns
Color
Pattern
Description
Green
steady
Start-up
1s on / 5s off
Fault free operation (“life pulse”)
flashing
Bus traffic
Orange
steady
Device is in on-event addressing mode (Timeout 60s)
1s on / 5s off
Backup mode entered
Red
steady
Mechanical fault / device jammed
flashing fast
Sensor error: Pressure tubes interchanged or “invalid configuration”
flashing slowly
Sensor error: Internal read error
1s on / 5s off
Internal error
Resetting the device by push button
The VAV compact controllers can be reset by push-button:
1. Press button for >10s → LED starts flashing orange
2. Release button while LED still flashes → LED keeps flashing for 3s
3. After those 3s → LED shines red (reset), then green (start-up).
A factory reset by push-button leads to a reset of all parameters as described in the section
“Commissioning and parameterization” to the OEM default values. Since these default val-
ues can be changed by the OEM, they are not necessarily the same as the Siemens factory
settings.
All other parameters, especially the bus parameters, are reset to Siemens factory settings.
VAV Compact Controllers can also be reset by the VAV handheld tool AST20 or over bus.
Please refer to the corresponding operating manual / technical basics.