Basic Documentation
10 / 42
Siemens VAV Compact Controller Modbus RTU A6V10631862_en--_e
Smart Infrastructure 2021-10-26
2.4 Human-machine interface
2.4.1 HMI parts and description
Activity
Push-button operation
Confirmation
Display current address
(in backward order)
Press button < 1s
Current address is displayed
Enter push-button addressing
mode
Press button > 1s and < 5s
Red LED shines (release button
before LED gets dark)
Reset to OEM default settings
Press button > 10s
Orange LED flashes
Color
Pattern
Description
Green
steady
Start-up
1s on 5s off
Fault free operation (“life pulse”)
flashing
Bus traffic
1)
Orange
steady
Device is in on-event addressing mode
1s on 5s off
Backup mode entered
Red
steady
Mechanical fault / device jammed
flashing fast
Sensor error: Pressure tubes interchanged or „Invalid
configuration“
flashing slowly
Sensor error: Internal read error
1s on 5s off
Internal error
1)
LED color is orange flashing for devices from Rev. A, cf. 1.1
2.4.2 Factory reset
The VAV Compact Controllers can be reset by push-button:
1. Press button for >10s → LED starts flashing orange
2. Release button while LED still flashes → LED keeps flashing for 3s
3. After those 3s → LED shines red (reset), then green (start-up).
A factory reset by push-button leads to a reset of all parameters as described in
the section 5.1 to the OEM default values. Since these values can be set by the
OEM, they are not necessarily the same as the Siemens factory settings.
All other parameters, especially the bus parameters, are reset to Siemens factory
settings.
VAV Compact Controllers can also be reset by the VAV handheld tool AST20 or
over bus. Please refer to the corresponding operating manual / technical basics.
Push button operations
LED colors and patterns
Factory reset