Data Sheet for Product

5 / 12
CE1N3547en_e Siemens
2021-10-20 Smart Infrastructure
Operating modes
Volume flow control (VAV or CAV)
Variable air volume (VAV) control: the operating point is determined by the setpoint value
and the Vmin / Vmax settings (cf. diagram below). Constant air volume (CAV) control is
achieved by sending a constant setpoint or by setting Vmin = Vmax.
1 Setpoint range
2 Actual value range
3 Controlled area
Position control
The VAV compact controllers can be operated as damper actuators, i.e. using the 0..100%
setpoint as position damper setpoint, by setting the operating mode parameter to “POS”.
Commissioning and parameterization
Parameterization of the VAV application
VAV application parameters are set by the OEM over the PPS2 interface (using ACS931 or
AST20). Some of them can be adjusted during commissioning, operation, or maintenance
and are accessible over a bus connection alternatively.
Parameter
Range
Description
Factory settings
Operating mode
VAV / POS
VAV: setpoint = volume flow 0…100%
POS: setpoint = damper position 0...100%
VAV
Opening direction
CW (R) / CCW (L)
Opening direction of air damper
CW (R)
Adaptive positioning
Off / On
Adaption of actual (if mech. limited) opening range
to position feedback 0...100%
1)
Off = No adaption / On = Pos. adaption
Off
Vmin
-20100%
Minimum air volume flow, rel. to Vnom
0 %
Vmax
20120%
Maximum air volume flow, rel. to Vnom
100 %
Vnom
0…60‘000 m
3
/h
Nominal air volume flow
2)
100 m
3
/h
Box coefficient (Vn)
13.16
VAV box characteristic value, defined by the OEM
1.00
Altitude /
Elevation asl.
05000m
in 500m steps
Correction factor for diff. pressure sensor (select
n*500m value closest to local altitude)
500 m
1)
Adaptation must not be activated while a device jam is present
2)
Value used for displaying / not used for volume flow control loop
Vmax [%]Vmin [%]
3