Data Sheet for Product
    5 / 12 
CE1N3547en_e    Siemens 
2021-10-20    Smart Infrastructure 
Operating modes 
Volume flow control (VAV or CAV) 
Variable air volume (VAV) control: the operating point is determined by the setpoint value 
and the Vmin / Vmax settings (cf. diagram below). Constant air volume (CAV) control is 
achieved by sending a constant setpoint or by setting Vmin = Vmax. 
1  Setpoint range 
2  Actual value range 
3  Controlled area 
Position control 
The VAV compact controllers can be operated as damper actuators, i.e. using the 0..100% 
setpoint as position damper setpoint, by setting the operating mode parameter to “POS”. 
Commissioning and parameterization 
Parameterization of the VAV application 
VAV application parameters are set by the OEM over the PPS2 interface (using ACS931 or 
AST20). Some of them can be adjusted during commissioning, operation, or maintenance 
and are accessible over a bus connection alternatively. 
Parameter 
Range 
Description 
Factory settings 
Operating mode 
VAV / POS  
VAV: setpoint = volume flow 0…100% 
POS: setpoint = damper position 0...100% 
VAV 
Opening direction 
CW (R) / CCW (L)  
Opening direction of air damper 
CW (R) 
Adaptive positioning 
Off / On 
Adaption of actual (if mech. limited) opening range 
to position feedback 0...100% 
1)
Off = No adaption / On = Pos. adaption 
Off 
Vmin 
-20…100% 
Minimum air volume flow, rel. to Vnom 
0 % 
Vmax 
20…120% 
Maximum air volume flow, rel. to Vnom 
100 % 
Vnom 
0…60‘000 m
3
/h 
Nominal air volume flow 
2)
100 m
3
/h 
Box coefficient (Vn) 
1…3.16 
VAV box characteristic value, defined by the OEM 
1.00 
Altitude /  
Elevation asl. 
0…5000m 
in 500m steps 
Correction factor for diff. pressure sensor (select 
n*500m value closest to local altitude) 
500 m 
1) 
Adaptation must not be activated while a device jam is present 
2) 
Value used for displaying / not used for volume flow control loop
Vmax [%]Vmin [%]
3