OpenAir™ VAV Compact Controller KNX / PL-Link G..B181..KN VAV Compact Controller 5 / 10 Nm with KNX communication • • • • • • • CE1N3547en_e 2021-10-20 GDB181..KN with 5 Nm nominal torque GLB181..
Type summary Product no. Stock no. GDB181.1E/KN S55499-D134 GDB181.1EMKN S55499-D505 GLB181.1E/KN S55499-D134 GLB181.1EMKN S55499-D263 Torque Packaging unit Operating voltage Power consumption Manual adjuster Position feedback 1 Stk. 5 Nm 10 Nm 18 Stk.2) AC 24 V 1 Stk. 1 VA / 0,5 W 3 VA / 2,5 W 1) True Position Potentiometer Yes 18 Stk. Please refer to data sheet N4698 for information on accessories and spare parts. 1) Actuator rotates 2) Contains additional 18 pcs. ASK78.
Notes Limitations VAV compact controllers are not suitable for environments where the air is saturated with sticky or fatty particles or contain aggressive substances. Safety Caution National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. • Observe national provisions and comply with the appropriate safety regulations. Mounting • Do not open the damper actuators.
HMI (Human-Machine Interface) Push-button operation Activity Push-button operation Confirmation Enter / leave addressing mode Press button < 1s LED turns red or turns off Reset to factory settings Press button > 20s LED flashes orange until device restarts Press key >2s and < 20s LED flashes 1x orange PL-Link connection test 1) 1) Function or part of the function available in PL-Link operation only LED colors and patterns Color Pattern Description Off --- Fault free operation or device no
Operating modes Volume flow control (VAV or CAV) Variable air volume (VAV) control: the operating point is determined by the setpoint value and the Vmin / Vmax settings (cf. diagram below). Constant air volume (CAV) control is achieved by sending a constant setpoint or by setting Vmin = Vmax. Vmin [%] Vmax [%] 1 Setpoint range 2 Actual value range 3 Controlled area 3 Position control The VAV compact controllers can be operated as damper actuators, i.e. using the 0..
Parameterization of the KNX integration KNX integration parameters are checked or set during engineering and commissioning in the ETS engineering tool. Parameter Range Description Factory settings VAV / POS VAV: setpoint = volume flow 0…100% VAV Tab card “standard” Operating mode POS: setpoint = damper position 0…100% Adaptive positioning On / Off Adaption of actual (if mech. limited) opening range Off to position feedback 0...100% 1) Off = No adaption / On = Pos.
KNX Group Objects Group Objects Table Nr. Name in ETS Object function Flags C R W T U ID Data point type KNX DPT_Name Format Unit Range 1 Fault information Transmit 1 1 0 1 0 219.001 _AlarmInfo 6 Byte --- cf. Description next page 2 Fault state Transmit 1 1 0 1 0 1.005 _Alarm 1 bit --- 0 = No alarm 1 = Alarm 3 Fault transmission Receive 1 0 1 0 1 1.003 _Enable 1 bit --- 0 = Disable 1 = Enable 4 Setpoint Receive 1 1 1 0 1 5.
Group Objects Description 1 Fault information If group object #3 ”fault transmission” is set to “on”, the following faults can be transmitted if they occur. In that case, group object #2 value changes to “alarm”. Error Group obj. #1 Description Resolution Device jammed XX 00 0A 03 0C 05 Target position can’t be reached due to blockage. Remove blockage (visual inspection required) or invert Opening direction if it is set wrongly.
Technical data Power supply Operating voltage G..B181.1E.. AC 24 V ± 20 % (SELV) or AC 24 V class 2 (US) Frequency Power consumption 50/60 Hz at 50 Hz Actuator holds 1 VA / 0.5 W Actuator rotates 3 VA / 2.5 W Function data Positioning time for nominal rotation angle G..B181.1E.. Nominal torque GDB.. 5 Nm GLB.. 10 Nm GDB.. < 7 Nm GLB..
Directives and Standards Product standard EN60730-x Electromagnetic compatibility (Application) For residential, commercial and industrial environments EU Conformity (CE) RCM Conformity UL, cUL GDB181.1E/KN GLB181.1E/KN A5W00003842 1) A5W00000176 1) 1) A5W00000177 1) A5W00003843 AC 24 V UL 873 http://ul.
Diagrams Internal diagrams The VAV compact controller is supplied with two prewired connecting and communication cables. G..B181..
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies Document ID CE1N3547en_e Edition 2021-10-20 © Siemens Switzerland Ltd, 2017 Technical specifications and availability subject to change without notice.