Basic Documentation

38 / 46
Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en
Smart Infrastructure 2021-10-25
9.3 S-mode group objects
9.3.1 Group objects list
Nr.
Name in ETS
Object
function
Flags
Data point type KNX
Range
C
R
W
T
U
ID
DPT_Name
Format
Unit
1
Fault information
Transmit
1
1
0
1
0
219.001
_AlarmInfo
6 Byte
---
[0...255 ] = Log Nr.
[0...2] = Alarm priority
[0...14] = Application area
[0...4] = Error class
[0...7] = Attributes
[0...7] = Alarm status
2
Fault state
Transmit
1
1
0
1
0
1.005
_Alarm
1 bit
---
0 = No alarm
1 = Alarm
3
Fault transmission
Receive
1
0
1
0
1
1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
4
Setpoint
Receive
1
1
1
0
1
5.001
_Scaling
1 Byte
%
0...100%
5
Damper position
Transmit
1
1
0
1
0
5.001
_ Scaling
1 Byte
%
0...100%
6
Volume flow
relative
Transmit
1
1
0
1
0
5.001
_ Scaling
1 Byte
%
0...100%
Transmit
1
1
0
1
0
8.010
_Percent_V16
2 Bytes
%
-327.68...327.67%
Transmit
1
1
0
1
0
5.004
_ Percent_U8
1 Byte
%
0…255%
7
Volume flow
absolute
1)
Transmit
1
1
0
1
0
9.009
_Value_Airflow
2 Bytes
m
3
/h
-670 760...670 760 m3/h
Transmit
1
1
0
1
0
14.077
_ Volume_Flux
4 Bytes
m
3
/s
0...(2
32
-1)
8
Fault
Transmit
1
1
0
1
0
1.005
_Alarm
1 bit
---
0 = No alarm
1 = Alarm
9
Overridden
Transmit
1
1
0
1
0
1.002
_Bool
1 bit
---
0 = False
1 = True
10
Override position 1
Receive
1
1
1
0
1
1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
11
Override position 2
Receive
1
1
1
0
1
1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
12
Balancing mode
Receive
1
1
1
0
0
1.003
_Enable
1 bit
---
0 = Disable
1 = Enable
13
Vmin
Receive
1
1
1
0
1
8.010
_Percent_V16
2 Bytes
%
-327.68...327.67%
14
Vmax
Receive
1
1
1
0
1
8.010
_Percent_V16
2 Bytes
%
-327.68…327.67%
15
Vnom
Read-only
1
1
0
0
0
9.009
_Value_Airflow
2 Bytes
m3/h
-670 760...670 760 m3/h
16
Opening direction
Read-only
1
1
0
0
0
1.012
_Invert
1 bit
---
0 = Not Inverted
1 = Inverted
17
Diff. pressure
2)
Read-only
1
1
0
0
0
9.006
_Value_Pres
2 Bytes
Pa
0..670 760 Pa
Read-only
1
1
0
0
0
14.058
_Value_Pressure
4 Bytes
Pa
0...(2
32
-1)
18
Coefficient
Read-only
1
1
0
0
0
14.*
4-Byte Float
4 Bytes
---
0...3.16
19
OEM-Reset
Receive
1
0
1
0
0
1.017
_Trigger
1 bit
---
0, 1 = Trigger
1)
For some group objects,
alternative data point types (DPT) can be selected in ETS. The first entry indicates the default setting.