9.2 Engineering tool parameters
9.2.1 ETS Parameters
Parameter
Range
Description
Factory
settings
Tab card “standard”
Operating mode
VAV / POS
VAV: setpoint = volume flow 0…100%
POS: setpoint = damper position 0…100%
VAV
Adaptive positioning
On / Off
Adaption of actual (if mech. limited) opening
range to position feedback 0...100%
Off = No adaptation / On = Pos. adaptation
Off
Altitude /
Elevation asl.
05000m
in 500m steps
Correction factor for diff. pressure sensor
(select n*500m value closest to local
altitude)
500 m
Backup timeout
0..60 min
0 min = disabled
Time interval to detect communication
interruption. If disabled, the actuator drives
to the last received setpoint until a new
setpoint is received.
30 min.
Backup mode
Backup position
Keep last position
Actuator behavior when the communication
timeout has been exceeded (no setpoint
received within the defined time interval).
Backup position: Actuator drives to
defined position
Keep last position: Actuator keeps
position without flow control
Backup
position
Backup position
0…100%
Position the damper drives to in case of
communication interruption
50%
Tab card “advanced”
Hysteresis (COV)
1)
volume flow
1...20%
Threshold for the relative volume flow.
COV below this value are not sent over the
bus.
1%
Min. repetition time
volume flow
10...900 s
Minimum waiting time until a COV above the
hysteresis threshold is sent over the bus
10 s
Hysteresis (COV)
damper position
1...20%
Threshold for the damper position. COV
below this value are not sent over the bus
1%
Min. repetition time
damper position
10...900 s
Minimum waiting time until a COV above the
hysteresis threshold is sent over the bus
10 s
Override position 1
2)
0...100%
Damper position which can be triggered by
the corresponding group object
0%
Override position 2
2)
0…100%
Damper position which can be triggered by
the corresponding group object
100%
Write Vnom
On / Off
If active, the group object for Vnom is
writable (OEM parameter protection
applies), otherwise it is read-only.
Off
Write Opening
Direction
On / Off
If active, the group object for the opening
direction is writable (OEM parameter
protection applies), otherwise it is read-only.
Off
1)
Adaptive positioning must not be activated while the actuator is mechanically jammed
2)
Override position 1 has priority over Override position 2
9.2.2 Additional ACS790 Parameters
Parameter
Range
Description
Factory
settings
Type of air
Outside air, Primary
supply air, Supply air,
Extract air
Type of air according to
EN13779:2007
Outside air
Master/Slave
Autonomous, Master,
Slave
Output signal of the supply air VAV
controller is the reference signal for
the extract air VAV controller.
Autonomous