Basic Documentation

31 / 46
Siemens VAV compact controller KNX/PL-Link G..B181.1E/KN CE1P3547en
Smart Infrastructure 2021-10-252021-10-25
6.3.3 KNX LTE-mode commissioning
VAV compact controllers, KNX LTE-mode controller and operating units are
connected to the power supply. Refresh, and then open the ACS790 device list.
variant 1 (with collected address labels)
1. Select a VAV compact controller from the device list by ID
(IDs are collected during mounting),
2. Double click the selected row to open the dialog box
“Address assignment”,
or
variant 2
1. Set a VAV compact controller to addressing mode
(Push button on device LED shines red)
2. In ACS790, click buttonProgramming mode” Address assignment
enter physical address click “Write”
Enter a physical address and short description for the selected VAV compact
controller,
Click “Write” to close dialog box,
Repeat steps for all VAV compact controllers for commissioning.
Continue: Further configuration with ACS790.
6.3.4 PL-Link commissioning
Multiple VAV compact controllers can be connected simultaneously to the power
supply or individually. For plug&play commissioning, the PL-Link capable
automation station must be preconfigured as described in section 6.2.3.
The PL-Link automation station is online.
The VAV compact controllers are not connected to the power supply.
Simultaneously connect all VAV compact controllers to the power supply (or
individually as applicable)
PL-Link automation station and VAV compact controllers execute registration
and address assignment. Configuration is uploaded from the automation
station to the VAV compact controllers.
Optional: Middle key press for connection test (>2 sec and <20 sec).