Data Sheet for Product

10 / 12
Siemens A6V10631834_en--_f
Smart Infrastructure 2021-10-20
Diagrams
Internal diagrams
The VAV compact controller is supplied with two prewired connecting and communication
cables.
G..B181..BA
Tool = Configuration and maintenance interface
(7-pin)
Power supply and communication cables
Core designation
Core color
Terminal code
Description
Cable 1: Power / black sheathing
1
red (RD)
G
System voltage AC 24 V
2
black (BK)
G0
System neutral AC 24 V
Cable 2: Communication / blue sheathing
6
violet (VT)
REF
Reference
8
grey (GY)
+
Bus (BACnet MS/TP)
9
pink (PK)
-
Bus (BACnet MS/TP)
Note
The operating voltage at terminals G and G0 must comply with the requirements under
SELV or PELV.
Safety transformers with twofold insulation as per EN 61558 required; they must be designed
to be on 100 % of the time.