Data Sheet for Product

6
Siemens
CE1N3544en
Smart Infrastructure
2021-10-25
Parameter
Range
Description
Factory setting
Operating mode
CON (VAV operation) /
3P (pos. control) /
STP (step control)
Interpretation of setpoint
CON = continuous setpoint for air volume flow [%]
3P = 3-position setpoint for damper position
STP = Min-Mid-Max control for volume flow
CON / VAV mode
Opening direction
(DIR)
r / L
(CW / CCW)
Opening direction of air damper
r (CW)
Adaptive positioning
(ADP)
Off / On
Adaption of actual opening range to position feedback
0…100 %
Off = No Adaption / 0…90° → 0…100 %
On = Pos. adaption / mapping, e.g., 0…60° → 0…100 %
Off
Range YC signal
0…10 V / 2…10 V
Setpoint for air volume flow
0…10 V
(CON / VAV mode)
Range U signal
0…10 V / 2…10 V
Actual value, according to selected U
0…10 V
U signal
FLW / POS
Actual value (measured)
FLW = Air volume flow [%]
POS = Damper position [%]
FLW
Time constant U
0.05…5 s
Smoothing constant actual value U
1 s
Vnom
0…60,000 m
3
/h
Nominal air volume flow
100 m
3
/h
Vmin
-20…100 %
Minimum air volume flow
0 %
Vmid
0%…100 %
Mid air volume flow
(only for STP operating mode)
50 %
Vmax
20…120 %
Maximum air volume flow
100 %
Box coefficient
(Vn value)
1…3.16
Characteristic value for air volume flow at nominal differential
pressure; set by the VAV box manufacturer.
1.00
Elevation asl
0…5000m
in 500 m (100 m) increments
Altitude level correction factor for differential pressure sensor
500 m