Data Sheet for Product

10
Siemens
CE1N3544en
Smart Infrastructure
2021-10-25
Power supply
Operating voltage
AC 24 V ± 20 % (SELV) or
AC 24V class 2 (US)
Frequency
50 Hz / 60 Hz
Power consumption
at 50 Hz
Rotating
3 VA / 2.5 W
Holding
1 VA / 0.5 W
Function data
Runtime for nominal rotation angle 90°
150 s (50 Hz) / 125 s (60 Hz)
Torque
Nominal
GDB181.1E/3
5 Nm
GLB181.1E/3
10 Nm
Maximum
GDB181.1E/3
<7 Nm
GLB181.1E/3
<14 Nm
Rotation angle
Nominal
90°
Maximum
95° ± 2°
Rotation direction
Clockwise (CW) /
Counter-clockwise (CCW)
(adjustable by tool)
Inputs
YC
(core 8)
Air volume flow reference or
communication signal
Input voltage
DC 0/2…10 V
Max. permissible input voltage
DC 35 V
Y1
Y2
(core 6)
(core 7)
Reference signals contact sensing
Contact open
DC 30 V contact voltage
Contact closed
DC 0 V, 8 mA contact current
U
(core 9)
Air volume flow measuring signal
Output voltage
DC 0/2…10 V limited to DC 12 V
Max. output current
DC ±1 mA
Connecting cable
Cable length
0.9 m
Power supply / communication
Cores and cross-sectional area
6 x 0.75 mm
2
Configuration and service interface
Terminal strip
7-pin, grid 2.00 mm
Degree of protection and safety class
Degree of protection
IP54 as per EN 60529
(see mounting instructions)
Safety class
III to EN 60730
Environmental conditions
Applicable standard
IEC 60721-3-x
Operation
Climatic conditions
Class 3K5
Mounting location
Indoors
Temperature
0…50 °C
Humidity (non-condensing)
5…95 % r.h.
Transport
Climatic conditions
Class 2K3
Temperature
-25…70 °C
Humidity
5…95 % r.h.
Storage
Climatic conditions
Class 1K3
Temperature
-5…45 °C
Humidity
5…95 % r.h.