Data Sheet for Product
4 / 10
Siemens A6V10636202_en--_b
Building Technologies 2016-12-14
Engineering
Potentiometer and auxiliary switches
Potentiometer and auxiliary switches cannot be added in the field.
Installation
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The actuators GLB..1E are maintenance-free.
Disposal
The device is considered an electronics device for disposal in terms of Eu-
ropean Directive 2012/19/EU and may not be disposed of as domestic gar-
bage.
● Dispose of the device through channels provided for this purpose.
● Comply with all local and currently applicable laws and regulations..
Technical data
Power supply (GLB1..1E)
Operating voltage (SELV/PELV) / Frequency AC 24 V ~ ±20 % (19.2…28.8 V ~) / 50/60 Hz
DC 24…48 V ⎓ ±20 % (19.2…57.6 V ⎓)
1)
Power consumption running GLB14..1E,
GLB16..1E
2.2 VA / 1.3 W
2.5 VA / 1.5 W
Power consumption holding GLB14..1E,
GLB16..1E
0.5 W
0.7 W
Power supply (GLB3..1E)
Operating voltage / Frequency AC 100…240 V ~ ±10 % (90…264 V ~) / 50/60 Hz
Power consumption running GLB34..1E,
GLB36..1E
6 VA / 2 W
4 VA / 1.5 W
Power consumption holding GLB34..1E,
GLB36..1E
0.9 W
0.6 W
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
10 Nm
16 Nm
10 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ± 2°
Runtime for 90° rotary angle 150 s
Actuator sound power level 28 dB(A)
1)
C-UL: Permitted only to DC 30 V ⎓