Data Sheet for Product
9
Siemens
A6V12513940_en
--
_a
Smart Infrastructure
2021
-
06
-
17
Set address „5“:
1. Enable addressing mode.
2. Set 1-digit: Press button 5 x..
● LED flashes rot for each press of the button.
3. Save address (skip 10-digit and 100-digit): Hold button.
● LED is lit rot.
– Release button.
⇒
The address is saved and is repeated 1 x for confirmation.
Modbus registers
Reg. Name R/W
Range/Listing Factory setting
Process values
1 Setpoint RW 0...100 % = 0...10000 -
2 Forced control RW 0 = Off / 1 = Open / 2 = Close / 3 = Stop
3 Actual Value R 0...100 % = 0...10000
256 Command RW 0 = Ready or calibrating / 1 = No available / 2 =
Self-test / 3 = Reinitialize / 4 = Remote reset
Parameter
260 MinPosition R 0...100 % = 0...10000 0 %
261 MaxPosition R 0...100 % = 0...10000 100 %
262 Actuator runtime R Compare technical data of respective actuator
513 Backup mode
(replacement mode)
RW 0 = Go to backup position / 1 = Not available / 2 =
Deactivated
2 = Deactivated
514 Backup position RW 0...100 % = 0...10000 0 %
515 Backup timeout RW 0...65535 900 s
516 Start-up setpoint RW 0...100 % = 0...10000 0 %
764 Modbus address RW 1...248 / 255 = "Unassigned" 255 =
"Unassigned"
765 Baud rate RW 0 = Auto / 1 = 9600 / 2 = 19200 / 3 = 38400 / 4 =
57600 / 5 = 76800 / 6 = 115200
0
766 Transmission format RW 0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2-
0
767 Bus termination RW 0 = Off / 1 = On
120 Ω electronically switchable
0
768 Bus conf. command RW 0 = Ready / 1 = Load / 2 = Discard 0
769 Status R
See Register 769 "State" [▶ 10]
-