Enter address using pushbutton
Display current address (starting from lowest address position)
The Modbus address can be set without an extra tool using pushbutton addressing.
To display the current Modbus address, press the button <1s.
Colors
1-digit: red 10-digit: green 100-digit: orange
Example for address 124:
LED
Note The address is entered and displayed beginning at the lowest digit (1st digit), see figure
above.
(Example: 124 starts with 4 x red)
Enter new address (starting from lowest address position)
1. Enable addressing mode: Press button > 1 s.
● LED is red.
– Release pushbutton (before LED turns off).
2. Enter digits: Press button n-times.
● LED flashes 1 x for each press of the button as feedback.
1st digit: red / 2nd digit: green / 3rd digit: orange.
3. Save digits: Hold pushbutton.
● LED lights in the color of the following digits.
– Release pushbutton.
4. Save address: Hold pushbutton.
● LED is red (confirmation).
– Release pushbutton.
⇒
The entered address is indicated again 1 x for confirmation.
The address is discarded if the button is released before the LED lights redn.