LED colors and flashing patterns
Color Blinking pattern Description
Green 1 s on / 5 s off Normal mode without bus traffic
Flickering Normal mode with bus traffic
Orange / green 1 s orange / 1 s green Device is in override control mode
Orange 1 s on / 1 s off Bus parameter not yet configured
1 s on / 5 s off Device is in backup mode (replacement
mode)
Red Permanently lit Mechanical error, device blocked, manual
intervention or calibration
1 s on / 5 s off Internal error
0.1 s on / 1 s off Invalid configuration, e.g. Min = Max
Blue Flickers 1 x after indicating the address Bus termination active
Reset actuator with pushbutton
1. Press button > 10 s.
● LED flashes orange.
2. Release button while LED is still flashing.
● LED flashes another 3 s.
3. Press button within these 3 s.
● Reset is cancelled.
4. Press button after these 3 s.
⇒
LED is red (Reset) while the device restarts.