Data Sheet for Product

5
Siemens
A6V12513940_en
--
_a
Smart Infrastructure
2021
-
06
-
17
User interface
Pushbutton operation
Action Pushbutton operation Feedback message
Return current Modbus address
(starting from lowest address
position)
Press button < 1 s 1st digit (single digit): red
10-digit (double digit): green
100-digit (triple digit): orange
LED blinks blue 1 x after the address
indication if bus termination is
switched on.
Example:
124 = 4 x red, 2 x green, 1 x orange
Switch on/off bus termination
Switch on Press button 3 x Blinking or flashing of LED stops
(termination mode).
Briefly press button 1 x Blue LED flashes 1 x.
Hold button until the LED turns red Red LED is lit (confirmation).
Release button LED not lit.
Address is indicated.
LED blinks blue 1 x after the address
indication.
Device enters normal mode.
Switch off Press button 3 x Blinking or flashing of LED stops
(termination mode).
Briefly press button 1 x Red LED is lit (confirmation).
Release button Device enters normal mode.
Enter Modbus address using
pushbutton
Press button > 1 s and < 5 s
See Enter address using pushbutton
[ 7]
Enable pushbutton addressing
(together with Climatix
TM
controllers)
Press button > 5 s and < 10 s Red LED is lit and goes off after 5 s.
Release button Orange LED lit.
Reset to factory settings Press button > 10 s LED flashes orange.