Data Sheet for Product
4
Siemens
A6V12513940_en
--
_a
Smart Infrastructure
2021
-
06
-
17
Commissioning
The devices were developed specifically for use with Climatix pushbutton configuration as
described in document CE1A3975
1)
.
The bus configuration can alternatively be configured by the local HMI, see section User in-
terface [▶ 5].
Check the following during commissioning:
● Bus configuration (address, baudrate, transmission mode, and optional bus termination).
The default address 255 allows mounting and commissioning of multiple actuators at the
same time without interfering with each other.
● Actuator parameters (Opening direction, position limits, position adaptation, etc.). The
value can be read over the Modbus register.
1)
Documents can be downloaded at http://siemens.com/bt/download.
Full or partial configuration via bus
The devices can be configured over bus if the pre-commissioning settings allow for a con-
nection between the Modbus master / programming tool and peripheral devices (i.e. non-
conflicting addresses and matching baudrate / transmission format).
● Full configuration via bus: A unique Modbus address can connect by the Modbus mas-
ter/programming tool after startup using the presets for transmission format and baud
rate (or auto-baud).
● Partial configuration over the bus: A Modbus address that is not unique must be first set
to a unique address, either by using the address input with pushbutton (see Enter ad-
dress using pushbutton [▶ 7]) or by setting the address to 246 by pressing the pushbut-
ton > 5s and < 10s (see Pushbutton operation [▶ 5]). The Modbus master/programming
tool can then connect after startup using the the presets for transmission format and
baud rate (or auto-baud).
The bus and actuator parameters can be set to target values on an existing connection over
the bus. For write operations to the bus parameters, "1 = Load" must be written to Reg 768
within 30 seconds; the changes are otherwise discarded.
Example: The table shows the register values before and after the change via bus access.
Register Name Before change After change
764 Modbus address 246 12
765 Baud rate 0 = Auto 1 = 9600
766 Transmission format 0 = 1-8-E-1 3 = 1-8-N-2
767 Bus termination 0 = Off 0 = Off
768 Bus conf. command 0 = Ready 1 = Load