Use
This document describes the network functions of the rotary actuators series G../MO.
Functions
Function Description
Communication Modbus RTU (RS-485), not galvanically isolated
Functions Setpoint 0...100 % valve setting
Actual value 0...100 % for valve setting
Override control Open / Close / Min / Max / Stop
Setpoint monitoring and backup mode
Supported baud rates 9.6 / 19.2 / 38.4 / 57.6 / 78.4 / 115.2 kBaud
Transmission formats 1-8-E-1, 1-8-N-1, 1-8-O-1, 1-8-N-2
Bus termination 120 Ω electronically switchable