Data Sheet for Product

11
Siemens
A6V12513940_en
--
_a
Smart Infrastructure
2021
-
06
-
17
Communication properties
Communication
Communication protocol Modbus RTU RS-485, not galvanically isolated
Number of nodes Max. 32
Address range 1...248 / 255
Factory setting
255
Transmission formats 1-8-E-1, 1-8-N-1, 1-8-O-1, 1-8-N-2
Factory setting
1-8-E-1
Baud rates (kbaud) Auto / 9.6 / 19.2 / 38.4 / 57.6 / 78.4 / 115.2
Factory setting
Auto
Bus termination 120 Ω electronically switchable
Factory setting
Off
Function description
Register 1/3 "Setpoint/actual value"
The controller setpoint for the position to move to, 0...100 % stroke/angle of rotation, scal-
ing 0.01, i.e. 0 % = 0 and 100 % = 10000
The actual value reported by the device, with the same scaling.
Register 256 "Restarting the device"
Restarting by:
resetting power (turning operating voltage off and on)
Sending "ReInitDevice" command.
Actuator restarts and sets all process values except actual value (= 50%) and setpoint (=
startup setpoint) to factory settings.
Register 256 "Self-test"
When triggered, the self test drives the actuator to the detected limits and sets the flags in
register 769 according to the result (bit 09 = 1 "failed" or bit 10 = 1 "passed").
The self-test fails, if the limits were not reached from the lower end (equates to a jam). Ex-
ceeding the min/max values does not fail the self-test.
The self-test can only be performed, if bit 04 = 0 in register 769 "Status", in other words,
there is currently no blockage or manual operation