User Manual
3
Siemens A6V11418678_en--_b
Smart Infrastructure 2020-05-26
Technical design
Housing
The housing is made of fiberglass reinforced plastic:
● Flame retardant
● Non-brominated
● Non-chlorinated.
Type summary
Type Stock number Open-loop
control
Operating voltage Positioning signal
input Y
Position indicator
U = DC 0...10 V ⎓
Self-adapting
rotary angle range
GLA161.9E/HR S55499-D444 Modulating AC 24 V ~ / DC 24 V ⎓ DC 0…10 V ⎓ yes yes
Accessories/spare parts
Individual spare parts are not available. Elements of the ASK77.3 mounting kit (accessory)
can, however, be used as spare parts.
Order text Components
ASK77.3 Accessory Kit BV for GLA161.03/HR Mounting bracket (base plate)
Shaft with sleeve and spring
Manual lever with safety clip
Equipment combinations
Control ball valves with externally threaded connection
1)
Type k
vs
[m
3
/h] DN Δp
max
Δp
a
2-port 3-port G..B
VAG61.15..
G 1 B 1…6.3 15
350
1400
VBG61.15.. -
VAG61.20..
G 1¼ B 4…10 20
1400
VBG61.20.. -
VAG61.25..
G 1½ B 6.3…16 25
1400
VBG61.25.. -
VAG61.32..
G 2 B 10…25 32
1000
VBG61.32.. -
VAG61.40..
G 2¼ B 16…40 40
800
VBG61.40.. -
VAG61.50..
G 2¾ B 25…63 50
600
VBG61.50.. -
1)
Data sheet N4212