Data Sheet for Product

4 / 8
Siemens A6V10636286_enAP_b
Building Technologies 2018-01-18
Installation
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The actuators GL..14..1E/RW are maintenance-free.
Disposal
The device is considered an electronics device for disposal in terms of Eu-
ropean Directive 2012/19/EU and may not be disposed of as domestic gar-
bage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations..
Technical data
Power supply GLD1..1E/RW GLA1..1E/RW
Operating voltage DC 24 V +25 % / -30 % (16.8…56.3 V )
1)
Power consumption Running 1.8 W 1.3 W
Holding 0.5 W 0. 5 W
Functional data GLD1..1E/RW GLA1..1E/RW
Nominal torque
Maximum torque (blocked)
8 Nm
16 Nm
10 Nm
16 Nm
Nominal rotary angle
Max. rotary angle
90°
95° ±
Runtime for 90° rotary angle 30 s 90 s
Actuator sound power level 28 dB(A)
Feedback potentiometer (GL..142.1E/RW only)
Change of resistance (wires P1-P2)
Load
0…5000 W
<0,25 W
Auxiliary switches (GL..146.1E/RW only)
Contact rating
Switching voltage
Switching range for auxiliary switches
Setting increments
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V
0.8 A resistive, 0.5 A inductive, min. 10 mA @ DC 60 V
DC 12…60 V
5°…90°
1)
C-UL: Permitted only to DC 30 V