User Manual
4 / 8
Siemens A6V10636286_en--_c
Building Technologies 2018-04-09
Installation
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The actuators GL..14..1E/RW are maintenance-free.
Disposal
The device is considered electrical and electronic equipment for dis-
posal in terms of the applicable European Directive and may not be
disposed of as domestic garbage.
∂ Dispose of the device through channels provided for this
purpose.
∂ Comply with all local and currently applicable laws and regu-
lations.
Technical data
Power supply GLD1..1E/RW GLA1..1E/RW
Operating voltage DC 24 V ⎓ +25 % / -30 % (16.8…56.3 V ⎓)
1)
Power consumption Running 1.8 W 1.3 W
Holding 0.5 W 0. 5 W
Functional data GLD1..1E/RW GLA1..1E/RW
Nominal torque
Maximum torque (blocked)
8 Nm
16 Nm
10 Nm
16 Nm
Nominal rotary angle
Max. rotary angle
90°
95° ± 2°
Runtime for 90° rotary angle 30 s 90 s
Actuator sound power level 32 dB(A) 30 dB(A)
Feedback potentiometer (GL..142.1E/RW only)
Change of resistance (wires P1-P2)
Load
0…5000 ς
<0,25 W
Auxiliary switches (GL..146.1E/RW only)
Contact rating
Switching voltage
Switching range for auxiliary switches
Setting increments
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V ⎓
0.8 A resistive, 0.5 A inductive, min. 10 mA @ DC 60 V ⎓
DC 12…60 V ⎓
5°…90°
5°
1)
C-UL: Permitted only to DC 30 V ⎓