Data Sheet for Product
GGD Electronic Damper Actuator Designed for UL Listed Fire/Smoke Control Dampers Technical Instructions
Document No. 152-046P25
July 20, 2015
Siemens Building Technologies, Inc. Page 3 of 5
Warning/Caution Notations
WARNING
Personal injury/loss of life may occur if you do
not perform a procedure as specified.
CAUTION:
Equipment damage may occur if you do not
follow a procedure as specified.
Accessories
985-006 Anti-rotation (mounting) bracket.
985-004
Self-centering shaft
adapter.
ASK74.1 Oversized shaft
adapter will accommodate
up to a 1.05-inch (26.6 mm)
diameter shaft. Use for
coupling to 1-inch
jackshafts that are slightly
oversized.
985-035P25 Conduit
adapter for accom-
modating a conduit
box (pk of 25).
985-008P20 Conduit
adapter for a 1/2-inch
(12 mm) NPT
connector (pk of 20).
Operation
When power is applied, the actuator coupling moves toward the open position, “90°”.
The actuator opens in fifteen seconds nominal, 90° at 60 Hz. In the event of a power
failure or when operating voltage is turned off, the actuator returns to the “0” position.
The return time is fifteen seconds maximum for 90°.
The GGD actuator does not require any periodic cycling to function properly as an
integral part of an active smoke control damper system.
NOTE: Siemens Industry, Inc. however, strongly suggests that all life safety
systems are functionally checked periodically. Check the smoke control
damper/actuator every time you functionally check your smoke detectors,
emergency lights, and/or power generators for operation.