User Manual
4
Siemens Datasheet A6V11948472_en--_a
Smart Infrastructure 2020-05-28
Technical data
Power supply
GED33..1A
Operating voltage (SELV/PELV) / Frequency
AC 220 V ~ ±10 % / 50/60 Hz
Power consumption running
15 VA
Power consumption holding
3 VA
Function data
GED33..1A
Nominal torque
Maximum torque (blocked)
16 Nm
19 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95°
Runtime for 90° rotary angle
22 s
Actuator sound power level
55 dB(A)
Connection cables
Cable length
0.9 m
Cross section of prewired connection cables
0.75 mm
2
Permissible length for signal lines
300 m
Degree of protection
Insulation class
As per EN 60730 II
Housing protection
IP 54 as per EN 60529
Environmental conditions
Operation
Climatic conditions
Mounting location
Temperature extended
Humidity (non-condensing)
IEC 60721-3-3
Class 3K5
interior, weather-protected
-10…+50 °C
< 95 % r.h.
Storage
Climatic conditions
Temperature extended
Humidity (non-condensing)
IEC 60721-3-1
Class 1K3
-15…+50 °C
<95 % r.h.
Standards, directives and approvals
Product standard
EN 60730
Part 2-14 / Particular requirements for electric
actuators
Electromagnetic compatibility
(Applications)
For use in residential, commercial, light-industrial
and industrial environments
EU Conformity (CE)
A5W00092743
Environmental compatibility
The product environmental declaration A5W00092776 contains data on environmentally compatible product
design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal).
Dimensions
Actuator W x H x D
See “Dimensions”, P5
Damper shaft
round
Square
Min. shaft length
Shaft hardness
10…21 mm
8…14 mm
20 mm
< 300 HV