User Manual

2
Siemens Datasheet A6V11948472_en--_a
Smart Infrastructure 2020-05-28
Use
The rotary actuators are used in ventilation and air conditioning plants to regulate and shut
off air dampers:
For damper areas up to 3 m
2
, friction-dependent
Suitable for three-position controllers (e.g. for outside air dampers).
Functions
GED.. AC 220 V
GED331.1A
GED332.1A
GED336.1A
Control type
Open-close / three-position
Rotary direction
Clockwise or counter-clockwise direction depends …
… on the type of control
… on the setting of the rotary direction switch.
With no power applied, the actuator remains in the respective position.
Position indication:
Mechanical
Rotary angle position indication by using a position indicator.
Position indication:
Electrical
-
The feedback
potentiometer can be
connected to external
voltage to indicate the
position.
-
Auxiliary switch
-
-
The switching points for
auxiliary switches can
be set in increments of
10° within 0° to 90°.
Manual adjustment
The actuator can be manually adjusted by pressing the gear train disengagement
button.
Rotary angle limitation
The rotary angle of the shaft adapter can be limited mechanically with a set screw.
Technical design
Housing
The housing consists essentially of fire-retardant UL94-5V ABS engineering plastic
Actuator motor / Gears
Brushless, robust DC motors ensure reliable operation regardless of load. The damper ac-
tuators do not require an end position switch, are overload proof, and remain in place upon
reaching the end stop.
The gears are maintenance free.
Type summary
Type
Stock no.
Nominal
Torque
Control
Operating
voltage
Feedback
potentiometer
10k
Aux. switches
Rotary
direction
switch
GED331.1A
S55499-D629
16 Nm
three-position
AC 220 V
-
-
yes
GED332.1A
S55499-D634
yes
-
GED336.1A
S55499-D635
-
2
cw ccw
GD..1E_Z06