Technical data 
Power supply (GEB1..1E) 
Operating voltage (SELV/PELV) 
AC 24 V ~ ± 20 % (19.2…28.8 V ~) 
DC 24…48 V ⎓ ± 20 % (19.2…57.6 V ⎓) 
1)
Frequency 
50/60 Hz 
Power consumption:  During 
operation 
GEB14..1E 
GEB16..1E 
2.3 VA / 1,1 W 
2.5 VA / 1.2 W 
    Holding 
GEB14..1E 
GEB16..1E 
0.5 W 
0.65 W 
Power supply (GEB3..1E) 
Operating voltage (SELV/PELV) 
AC 100…240 V ~ ± 10 % (90…264 V ~) 
Frequency 
50/60 Hz 
Power consumption:  During 
operation 
GEB34..1E 
GEB36..1E 
4 VA / 1.6 W 
3.4 VA / 1.3 W 
  Holding 
GEB34..1E 
GEB36..1E 
0.9 W 
0.6 W 
Function data 
Nominal torque 
  Maximum torque (when blocked) 
  Minimum holding torque 
20 Nm 
35 Nm 
2)
20 Nm 
Nominal rotation angle (with position indication) 
  Maximum rotation angle (mechanically limited) 
90° 
95° ± 2° 
Runtime at nominal rotation angle 90° 
150 s 
Actuator sound power level (at a positioning time of 150 s) 
<35 dB(A) 
Inputs 
Positioning signal for GEB14..1E 
  Operating voltage 
  AC 24 V ~ / DC 24…48 V ⎓ 
 (wires 1-6/G-Y1) 
 (wires 1-7/G-Y2) 
Clockwise 
Counterclockwise 
Positioning signal for GEB34..1E 
  Operating voltage 
  AC 100…240 V ~  
  (wires 1-6/G-Y1) 
  (wires 1-7/G-Y2) 
Clockwise 
Counterclockwise 
Positioning signal for GEB16..1E 
  Input voltage 
  Power consumption 
  Input resistance 
  (wires 8-2/Y-G0) 
DC 0/2…10 V ⎓ 
0.1 mA 
>100 kΩ 
Max. permissible input voltage 
  Protected against faulty wiring 
DC 35 V ⎓ limited internally to DC 10 V ⎓ 
Max. AC 24 V ~/ DC 24…48 V ⎓ 
Hysteresis 
for non-adjustable characteristic function 
for adjustable characteristic function 
60 mV 
0.6 % of ΔU 
Adjustable characteristic (GEB163.1E, GEB164.1E) 
Adjustable with 2 potentiometers: 
Offset Uo 
Span ΔU 
DC 0…5 V ⎓ 
DC 2…30 V ⎓ 
Max. input voltage 
Protected against faulty wiring 
DC 35 V ⎓ 
Max. AC 24 V ~ / DC 24…48 V ⎓ 
1)
 cUL: Only to DC 30 V ⎓ permissible 
2)
See notes on page 4 and page 8 