Data Sheet for Product

7
Siemens
A6V11449860_en--a
Smart Infrastructure
2019-09-10
Outputs
Position indicator
Output signal (GEB16..1E)
Output signal (GEB36..1E)
Output voltage U
Max. output current
(wires 9-2/U-G0)
(wires 9-2/U-G-)
DC 0…10 V
DC ± 1 mA
Protected against faulty wiring
Max. AC 24 V ~/ DC 24…48 V
Aux. power supply (G-/G+)
GEB36..
DC 24 V ± 20 %, max. 10 mA
Feedback potentiometer (for GEB142.1E)
Change in resistance
(wires P1-P2)
0…5000 Ω
Load
Max. contact current
Permissible voltage at potentiometer (SELV/PELV)
Insulation resistance between potentiometer and
housing
<0.25 W
<0.1 mA
AC 24 V ~ / DC 24…48 V
AC 500 V ~
Auxiliary switches (GEB146.1E, GEB166.1E, GEB346.1E)
Switching voltage
Contact loading
Electric strength auxiliary switch against housing
Switching range for auxiliary switches / setting
increments
AC 24…250 V ~ / DC 12…30 V
6 A resistive, 2 A inductive, min. 10 mA @ AC
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V
0.8 A resistive, 0.5 A inductive, min. 10 mA @ DC 60 V
AC 4 kV
5°…90° / 5°
Factory switch setting:
Switch A
Switch B
85°
Connection cables
Cable length
0.9 m
Cross-section
0.75 mm
2
Permissible length for signal wires
300 m
Safety class and degree of protection
Protection class
AC 24 V ~ / DC 24…48 V , feedback
potentiometer
AC 100…240 V ~, auxiliary switches
EN 60730
III
II
Degree of protection of housing
IP54 as per EN 60529 (see "Mounting", page 4, and
Mounting instructions A6V11476940)
Environmental conditions
Operation
Climatic conditions
Mounting location
Temperature
Humidity, non-condensing
IEC 60721-3-3
Class 3K5
interior, weather-protected
-32…55 °C
<95 % r.h.
Transportation
Climatic conditions
Temperature
Humidity, non-condensing
IEC 60721-3-2
Class 2K3
-32…70 °C
<95 % r.h.
Storage
Climatic conditions
Temperature
Humidity, non-condensing
IEC 60721-3-1
Class 1K3
-32…50 °C
<95 % r.h.
Mechanical conditions
Class 2M2