Data Sheet for Product
10
Siemens
A6V11449860_en--a
Smart Infrastructure
2019-09-10
Control on GEB3..1E (AC 100…240 V ~)
Open-close, single wire control
Single pole single throw (SPST)
Open-close, double wire control
Single pole double throw (SPDT)
3-position control
Modulating control
N
Y1
Y2
N
AC 100...240 V ~
N
Y1
Y2
N
AC 100...240 V ~
N
Y1
Y2
N
AC 100...240 V ~
N
L
Y
UG+
G-
AC 100...240 V ~
N
Cable designations
Connecting thread
Code
No.
Color
Abbreviation
Meaning
Actuators
AC 24 V ~ / DC 24…48 V ⎓
G
G0
Y1
Y2
Y
U
1
2
6
7
8
9
red
black
violet
orange
gray
pink
RD
BK
VT
OG
GY
PC
System potential AC 24 V ~ / DC 24…48 V ⎓
System zero
Positioning signal AC/DC 0 V, clockwise (GEB14..1E)
Positioning signal AC/DC 0 V, counterclockwise (GEB14..1E)
Signal input (GEB16..1E)
Signal output (GEB16..1E)
Actuators
AC 100…240 V ~
L
N
Y1
Y2
G+
G-
Y
U
3
4
6
7
1
2
8
9
brown
light blue
black
white
red
black
gray
pink
BR
BU
BK
WH
RD
BK
GY
PK
Phase, AC 100…240 V ~
Neutral conductor
Positioning signal AC 100…240 V ~, clockwise (GEB34..1E)
Positioning signal AC 100…240 V ~, counterclockwise (GEB34..1E)
System potential DC 24 V (auxiliary power) (GEB361.1E)
System neutral (auxiliary power) (GEB361.1E)
Signal input (GEB361.1E)
Signal output (GEB361.1E)
Feedback potentiometer
a
b
c
P1
P2
P3
white/red
white/blue
white/pink
WH RD
WH BU
WH PK
Potentiometer 0…100 % (P1-P2)
Potentiometer pick-off
Potentiometer 100…0 % (P3-P2)
Auxiliary switch
Q11
Q12
Q14
Q21
Q22
Q24
S1
S2
S3
S4
S5
S6
gray/red
gray/blue
gray/pink
black/red
black/blue
black/pink
GY RD
GY BU
GY PK
BK RD
BK BU
BK PK
Switch A input
Switch A NC contact
Switch A NO contact
Switch B input
Switch B Normally closed contact
Switch B NO contact