Function Description
Communication Modbus RTU (RS-485), not galvanically separated
Functions - Setpoint and actual position 0..100%
- Override control Open / Close / Min / Max / Stop
- Setpoint monitoring and backup mode
Supported baudrates 9.6, 19.2, 38.4, 57.6, 78.4, 115.2 kbaud
Supported transmission
formats
1-8-E-1, 1-8-N-1-, 1-8-O-1, 1-8-N-2
Termination 120 Ω electronically switchable
Type summary
Product no. Stock no. Operating
voltage
Positioning
signal
Power consumption Posit. time Manual
adjuster
Position
feedback
GEB161.1E/MO S55499-D298
AC 24 V Modbus RTU
6 VA / 5.5 W max.
1)
150 s Yes Yes
GIB161.1E/MO S55499-D299 8 VA / 8 W max.
1)
1)
max. = actuator rotates
Accessories / Spare parts
GEB.. Please refer to data sheet N4697
GIB.. Please refer to data sheet N4699
Ordering (Example)
Product no. Stock no. Description Amount
GEB161.1E/MO S55499-D298 Damper actuator Modbus 1
+ accessories (shaft inserts, etc.)
Equipment combinations
Product no. Stock no. Doc. type Doc. number
POL424.50/STD
POL424.70/STD
S55394-C245-A100
S55394-C247-A100
Datasheet Q3973
Operating manual P3973
POL635.00/STD BPZ:POL635.00/STD Datasheet Q3230
Operating manual P3903
POL638.00/STD
POL638.70/STD
BPZ: POL638.00/STD
S55396-C387-A100
Datasheet Q3900
Operating manual P3903