OpenAir Actuators without spring return GEB…1 Technical basics CM2Z4621en 2017-05-26 Building Technologies
/44 Siemens Building Technologies Actuators without spring return GEB…1 CM2Z4621en 2017-05-26
Table of contents 1 Introduction ................................................................................................... 5 1.1 Revision history............................................................................................. 5 1.2 About this document ..................................................................................... 5 1.3 Document contents .......................................................................................
7.3.1 HMI – Human-machine interface ................................................................ 28 7.3.2 Push button addressing ..............................................................................29 7.3.3 Commissioning ............................................................................................30 7.3.4 Modbus registers......................................................................................... 31 7.3.5 Parameter and function description ..................
1 Introduction 1.1 Revision history Changes Accessories (Ext. auxiliary switches ASC77..) Referenced documents (ASC77..) Electrical parallel connection of actuators Determining the actuator type Permissible line length and cross-sectional areas Environmental compatibility and disposal Referenced documents EU and RCM Conformity European Directive 2012/19/EU Added type GEB161.1E/MO 1.2 Date 10.01.2005 07.02.2005 26.02.2016 26.05.2017 Chapter Pages 2.2 6 11.2 33 4.2 16 4.4 18 6.1 20/21 10 31 11.
2 Introduction Non spring-return actuators This chapter provides information on application, functions, and device combinations. Furthermore, it contains a type overview and explains the actuator design including setting and operator elements for this family of actuators. 2.1 Application The actuators are used in ventilating and air conditioning plants to operate air dampers and air throttles: ∂ ∂ ∂ For damper areas up to 3 m 2, friction-dependent. Suitable for modulating controllers (DC 0...
2.2 Type summary The following table shows the options for the actuator types. GEB.... 131.1E 132.1E 136.1E 331.1E 332.1E 336.1E 161.1E X 166.1E X X X X DC 0...10 V X X X X DC 2...10 V X Operating voltage X AC 230 V X 161.1E/MO Modbus RTU X AC 24 V X 164.1E Modulating control Three-position control Operating voltage 163.1E X X Positioning signal input Y X DC 0...35 V with characteristic X X function Modbus RTU X Position indicator X U = DC 0...
2.3 Description of functions 2.3.1 Description of functions for GEB...1 The functions are listed in a table and are assigned to the respective control types. Type GEB13..1 / GEB33..1 GEB16..1 GEB161.1E/MO Control type Three-position control Modulating control. Modbus RTU Positioning signal with adjustable characteristic function Y = DC 0...35 V with - offset Uo = 0...5 V and span ΧU = 2...
2.3.2 Supplementary information on the description of functions for GEB16..1 Supplement The following information applies to modulating actuators. Characteristic function (GEB163.1, GEB164.1) Application Offset Uo and span ΧU can be adjusted using two potentiometers (see 3.4 "Adjustable characteristic function"). The maximum permissible input voltage (Uo + ΧU) is DC 35 V.
2.4 Controllers The actuators can be connected to all controllers having the following outputs. All safety-related requirements must be met (see chapter 4 "Engineering notes"). Actuator type Control type Controller output GEB13..1 Three-position AC 24 V GEB33..1 Three-position AC 230 V GEB16..1 Modulating GEB161.1E/MO Modbus RTU 2.5 DC 0...10 V / DC 2...10 V / DC 0...35 V Modbus RTU Structure and design Description The electronic motor-driven GEB..
Cover for DIL switch (only for GEB16..1) This cover protects the DIL switch against dust and water spray. Push button and LED at external Interface The HMI of networked types consists of a push button and an LED to allow certain interactions with the actuator or to provide visible feedback from the actuator. 2.
3 Introduction Technical design This chapter discusses the following topics: ∂ Motor technology. ∂ Adjustable auxiliary switches. ∂ Adjustable characteristic function (positioning signal, DC 0...35 V). ∂ Control characteristics by including the neutral zone 3.1 Motor technology Motor technology A synchronous motor enables accurate speed control. The magnetic coupling serves as a torque supervision to protect both actuator and dampers. 3.
3.3 Electrical functions Auxiliary switches and positioning signals The illustration below shows the relationship between the rotary angle, the adjustable switching points for auxiliary switches A and B, and the positioning signal.
3.4 A modulating positioning signal DC 0..35 V from a controller controls the actuator. The rotary angle is proportional to the positioning signal. Using potentiometer "Uo", you can set the offset for DC 0...5 V, and with potentiometer " ΧU", you can set the span for DC 2...30 V. Ys [%] 100 1) 4) 3) 2) Ys 4637D04 Actuators GEB163.1, GEB164.1 Adjustable characteristic function Uo 2 U U 10 16 30 24 0 1 U 2 5 10 Y Uo ΧU Examples as per the diagram 35 Y [V] 5 3 4 Uo Χ U (max.
Y S [%] 100 4637D02 Characteristic function for the example Max. positioning range Ysmax = Span Ys = Offset Uo = Span ΧU = 50 0 2 Uo U min 3.5 10 18 100 % (95°) 50 % (47.5°) 2V 16 V Y [V] Effective span ΧUw = Umax – Umin = 10 V - 2 V = 8 V ΧU (16 V) U max Neutral zone Actuators GEB16...1 (DC 0...10 V) For modulating control actuators, note the control characteristic for the selected switchon point of the setpoint.
4 Engineering notes Introduction Carefully study the basics of the control systems used before proceeding to the sections below, and pay special attention to all safety-related information. Intended use Use these actuators in a system only for applications as described in the basic system documentation of the control systems used. Additionally, note the actuator-specific properties and conditions as described in this chapter and in chapter 8 "Technical data" in this document. 4.
Operating voltage AC 24 V, AC 230 V The following regulations apply to these operating voltages: Operating voltage AC 24 V Operating voltage AC 230 V Specification on AC 24 V transformers Fuse of AC 24 V operating voltage Transformers, secondary side: ∂ According to the effective load of all connected devices. ∂ Line G (system potential) must always be fused. ∂ Where required, additional line G0 (system neutral).
4.3 Notes on EMC optimization Running cables in a duct Make sure to separate high-interference cables from equipment susceptible to interference. Cable types ∂ Cables emitting interference: ∂ Cables susceptible to interference: ∂ You can run both cable types in the same cable ducting, but in different compartments. If ducting with three closed sides and a partition is not available, separate the interference-emitting cables from other cables by a minimum of 150 mm or route in separate ducting.
The following diagram (example EMCO) allows for determining the total torque for this air damper type. 6 3 675 2 Damper height H [mm] 1 400 600 ta l 1005 To 4 pr 13 35 5 0 200 es su r e [P ] 16 65 7 4621D01en 19 95 8 20 00 100 9 0 0 Friction torque (excl.
5 Mounting notes Mounting instructions All information and steps to properly prepare and mount the actuator are available in the mounting instructions 4 319 0109 0 (M4621) delivered with the actuator. The shaft adapter as well as all other individual parts are not pre-mounted, as the actuator components are put together differently depending on damper shaft length. Refer to "2.5 "Structure and design" in this chapter.
6 Introduction Wiring notes Prior to wiring, study all information in the following sections: ∂ "Safety notes" in chapter 4.1 ∂ "Device-specific regulations" in chapter 4.2 ∂ "Notes on EMC optimization" in chapter 4.3 ∂ "Diagrams" in chapter 9, and the ∂ HVAC plant diagram. 6.1 Permissible line length and cross-sectional areas The line lengths and cross-sectional areas depend on the actuators power consumption and the permissible voltage drop of the connection lines to the actuators.
Line length/consumption AC 24 V The diagram applies to AC 24 V and shows the permissible line length L as a function of consumption P and as a parameter of the line cross sections. 4626D02en L [m] 300 200 2.5 mm² 0.75 mm² 100 1 mm² 1.5 mm² 0.5 mm² 0 8 0 Notes on diagram ∂ ∂ P&I diagram: Voltage drop on the supply lines 16 The values in [VA, W] on the P-axis are allocated to the permissible voltage drops (ΧU/2U = 4 %) on line L as per the above table and to the P&I diagram.
The following sections show how to determine the permissible line length and cross sections for the various actuators based on examples. The examples for actuators connected in parallel apply to the following arrangement: G0 G L2 A1 L2 A2 L2 A3 L2 A4 G0 G L1 G0 G Controller G0 L1 G G0 G G0 G Assumption 4614S01en Line length for actuators connected in parallel The line resistances of L2 are equal and can be ignored for L1.
6.3 Modulating actuators GEB16..1 Power consumption and perm. voltage drop with one actuator P&I diagram: Conduction currents Actuator wiring (modulating) With AC supply, the G0 line has a AC 0.23 A supply current and a DC 0.1 mA positioning signal current (from Y = DC 0...10 V). The AC voltage drop on the G0 line does not impact the positioning signal Y. Operating voltage Power consumption Perm. voltage drop for line 1 (G)2 (G0) AC 24 V 5.
6.4 Actuator wiring (Modbus RTU) The damper actuators are supplied with a prewired connecting and communication cable. All interconnected devices must be connected to the same G0. Strand code 1 2 6 8 9 Note Mechanical check Electrical check Description System potential AC 24 V System neutral AC 24 V Reference (Modbus RTU) Bus + (Modbus RTU) Bus - (Modbus RTU) Commissioning notes All information necessary for commissioning is contained in the following: ∂ This document ("Technical basics" Z4621en).
7.2 Rotary movement: Three-position control GEB13..1, GEB33..1 Electrical function check Check the actuator operating states as follows (see also chapter 9.3 Connection diagrams (three-position control)). Wire connections AC 24 V AC 230 V 1–6 4–6 1–7 4–7 1 – 6 / 1 – 7 open 4 – 6 / 4 – 7 open Rotary movement: Modulating control GEB16..1 Rotary direction Clockwise Counterclockwise Actuator stays in position reached. Check the actuator operating states as follows (see also chapter 9.
Self-adaptation ∂ 0 ∂ Positioning signal without characteristic function: (GEB161.1, GEB166.1) 2... ∂ 0... ∂ Positioning signal with/without characteristic function: (GEB163.1, GEB164.1) C 0 ∂ ∂ Alternative switch-on/switch-off of self-adaptation. : ON 0: OFF Factory setting: 0. Alternate setting: 2..: DC 2...10 V 0..: DC 0...10 V Factory setting: 0… Alternate setting: C: DC 0...35 V (Comfort, with characteristic function) 0: DC 0...10 V (without characteristic function) Factory setting: 0.
Push button operation 7.3 Modbus 7.3.1 HMI – Human-machine interface Activity Push-button operation Confirmation Display current address Press button < 1s 1-digits: red (starting with lowest address digit) 10-digits: green 100-digits: orange If termination is switched on, LED flashes 1x blue after address display Example: 124 = 4x red, 2x green, 1x orange Turn bus termination on / off turn on 1.press 3x LED flashing and flickering stops (termination mode) 2.
Resetting the device by push button 1. 2. 3. 4. Press button for >10s → LED starts flashing orange. Release button while LED still flashes → LED keeps flashing for 3s. If the button is pressed within these 3s, the reset is cancelled. After those 3s → LED shines red (reset), then the device restarts. 7.3.2 Push button addressing The Modbus address can be set without a separate tool by using push-button and LED. To display the current address, press button <1s.
Set address “5”: 1. Enter addressing mode 2. Set 1- digit: Press button 5-times → LED flashes green per button press Store address: press button until LED shines red → address is stored and displayed 1x for confirmation 7.3.3 Commissioning Workflow 1 The devices are especially designed for using the Climatix push-button configuration as described in document A3975 1). The bus configuration can alternatively be parameterized by the local HMI, cf. page 28.
7.3.4 Modbus registers Reg. Name R/W Unit Scaling Range / enumeration Process Values 1 Setpoint RW % 0.01 0..100 2 Override control RW -- -- 0 = Off / 1 = Open / 2 = Close 3 = Stop / 4 = GoToMin / 5 = GoToMax 3 Actual position R % 256 Command RW -- 0.01 0..
Reg. Name R/W Value Example Device information 1281 Factory Index R Two bytes, each 00 5A ⇓ 00 “Z” coding an ASCII char.
7.3.5 Parameter and function description Function Reg. Description Override control 2 The actuator can be operated in override control for commissioning / maintenance purposes or system-wide functions (e.g. night-cooling). ∂ Manual override: When the gear disengagement is used to freely adjust the damper position, a mechanical jam will be detected if a mismatch between setpoint and actual position persists for more than 10s.
8 AC 24 V supply (SELV/PELV) for GEB13..1, GEB16..1.. AC 230 V power supply for GEB33..1 Function data Technical data Operating voltage Frequency Safety extra-low voltage (SELV) or Protection by extra-low voltage (PELV) as per Requirements for external safety insulating transformer (100 % duty) Supply line fuse Power consumption GEB13..1: Running GEB16..1: Running GEB161.
Change of resistance (wires P1-P2) Load Max. sliding contact current Permissible voltage at potentiometer (SELV/PELV) Insulation resistance between potentiometer and housing Contact rating Life: 6 A resistive, 2 A inductive 5 A resistive, 1 A inductive without load Switching voltage Nominal current resistive/inductive Electric strength auxiliary switch against housing Switching range for auxiliary switches Setting increments Switching hysteresis Factory switch setting Switch A Switch B 0...
9.1 Internal diagrams AC 24 V AC 230 V 100% A B AC 24 V...230 V / 6 (2) A P1 P2 P3 100% M S1 (c) (Y1) 7 0...1000 ς (b) GEB33... 6 (Y2) S4 (Q11) (c) (b) (a) S1 AC 230 V (a) AC 24 V...230 V / 6 (2) A P1 P2 P3 (Y2) 7 (Y1) GEB33..1 0...1000 ς AC 0 V GEB13... 6 GEB13..
9.2 Cable labeling All wires are color-coded and labeled. Pin Code No. Actuators AC 24V G G0 Y1 Y2 1 2 6 7 Cable Color Abbreviation red RD black BK purple VT orange OG Y U REF + - 8 9 6 8 9 gray pink violet gray pink GY PK VT GY PK System potential AC 24 V System neutral Positioning signal AC 0 V, "clockwise" Positioning signal AC 0 V, "counterclockwise" Pos. signal DC 0...10 V, 2...10 V, 0...35 V Position indication DC 0...
9.3 SP 4621A01 GEB13..1 AC 24 V Connection diagrams (three-position control) (G) Q1 Q2 AC 24 V (G0) (Y1) (Y2) 6 7 N P1 P2 P3 S1 S4 GEB13... Y 1 S2 S3 S5 S6 S1 S4 SN L Controller Actuator GEB13..1 System potential AC 24 V System neutral Controller contacts N Y L N Q1, Q2 Controller Actuator GEB33..1 System potential AC 230 V System neutral Controller contacts 4621A02 GEB33..1 AC 230 V N Y SP SN Q1, Q2 (L) AC 230 V (N) Q1 Q2 (Y1) (Y2) 6 7 N P1 P2 P3 GEB33...
9.4 Connection diagrams (modulating) 9.4.1 Typical application The controller output is connected directly to the actuator input. GEB16..1 SP (G) AC 24 V (Y) 1 (G0) N 8 S1 S4 9 S2 S3 S5 S6 GEB16... 4621A04 Y 2 P SN 9.4.2 N Y P SP SN Controller Actuator GEB16..
9.5 Connection diagrams (networked) 9.5.1 Typical application The application controller is connected to the actuator by the bus cable. GEB161.1E/MO 10 General notes Environmental compatibility and disposal This actuator was developed and manufactured by using environmentally-compatible materials and by complying with our environmental standards.
11 Chapter contents Appendix This chapter contains: ∂ Actuator dimensions ∂ Referenced documents ∂ Feedback form min.100 11.1 Dimensions 141 10.6 42 20 113 Dia. 5 min.100 168 180 19 60 192 Taptite M6 x 16 2 Mounting bracket 30 min.100 4621M02en min.150 min.60 3 15 30 min.7 900 12 Dia. 6.4...20.5 Square 6.4...13 Dia. 10.5 31.5 81 60 GEB...1 Dimensions in mm 41/44 Siemens Building Technologies Technische Grundlagen: Drehantriebe GEB...
A6V101006034M01 External Modbus Interface X = 220 mm Dimensions in mm 42/44 Siemens Building Technologies Actuators without spring return GEB…1 CM2Z4621en 2017-05-26
11.2 Referenced documents Purpose of this listing The previous chapters contain all information relevant to safety and project-specific requirements, mounting, wiring, and commissioning of actuators. Documents and standards The following list contains all documents referenced by this document on basics: ∂ ∂ ∂ Data sheets (N....) with detailed specifications Basic documentation (Z....) with basics on air damper actuators Mounting instructions (M….
Standards HD 384 EN 61 558 EN 60 730 Electrical installations in buildings Safety of transformers, power supply units and similar equipment Automatic electrical controls for household and similar use Electromagnetic compatibility: Emissions IEC/EN 61 000-6-3 IEC/EN 61 000-6-1 IEC/EN 61 000-6-2 Electromagnetic compatibility: Immunity Electromagnetic compatibility: Immunity 89/336/EWG Directive on electromagnetic compatibility 73/23/EWG Low voltage directive Issued by Siemens Switzerland Ltd Building