Data Sheet for Product

OpenAir GDE Enhanced Non-Spring Return Rotary Electric Damper Actuator Technical Instructions
Document Number 155-784
January 20, 2017
Siemens Industry, Inc. Page 7
Control signal
adjustment,
continued
Figure 10.
Ys Positioning range (100% = angle of rotation 90°*)
Y Control input signal
Uo Offset (start point)
U Span
Uw Active voltage range (Ys changes)
* When the mechanical limitation of the angle of rotation
and self-adapt function are ON, 100% does not equal
90°. Also valid for control signal 0 to 10 Vdc.
Setting for
10 Vdc span
0 Vdc offset
Figure 11.
Table 2.
Examples in Figure 10
Positioning
Signal Y
Positioning
Range Ys
Settings
Uo
U
1. Minimum span
0 to 2 Vdc
0 to 100%
0 Vdc
2 Vdc
2. Limitation of rotation
0 to 10 Vdc
5 to 35 Vdc
0 to 17%
0 to 100%
5 Vdc
30 Vdc
3. Limitation of rotation
0 to 10 Vdc
0 to 30 Vdc
0 to 33%
0 to 100%
0 Vdc
30 Vdc
4. Setting shown in Figure 11.
0 to 10 Vdc
0 to 100%
0 Vdc
10 Vdc