Technical Instructions Document No. 155-188P25 EA GDE/GLB-2 December 26, 2007 OpenAir™ Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac Floating Control Description OpenAir direct coupled 24 Vac non-spring return rotary electric actuators are designed for floating control of dampers.
Technical Instructions Document No. 155-188P25 December 26, 2007 OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Power supply Operating voltage (G–Y1 or G–Y2) Frequency Power consumption 24 Vac +20%, -15% 50/60 Hz 2.3 VA Equipment rating Rating Class 2 according to UL, CSA Class III per EN60730 Auxiliary features Feedback potentiometer (GDE/GLB132.
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Technical Instructions Document No. 155-188P25 December 26, 2007 Specifications, Continued Ambient conditions Ambient temperature operation storage and transport Ambient humidity (non-condensing) Agency certification UL listed to UL873 cUL certified to Canadian Standard C22.2 No.
Technical Instructions Document No. 155-188P25 December 26, 2007 OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control ASK78.3U Shaft insert for use with 3/8-inch (8 to 10 mm) diameter shafts. (Included in box with GDE/GLB Series). (Pkg/10) NOTE: Factory installed 1/2-inch guide must be removed prior to installation. EA0807R1 Accessories, Continued Figure 5. Shaft Insert. EA1060R1 985-101P25 –Shaft guide insert, 1/2 inch 25 Pk (Factory installed with GDE/GLB Series).
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Technical Instructions Document No. 155-188P25 December 26, 2007 Actuator Components, Continued GDE131.1T Terminal Strip EA1094R1 The GDE131.1T uses a Terminal Strip connection for connection purposes rather than the cable connection. GDE131.1T NOTE: Wires are supplied by the customer. CW Supply 24Vac CCW Figure 11. GDE131.1N Post Header AMP The GDE131.
Technical Instructions Document No. 155-188P25 December 26, 2007 Operation OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control A floating control signal controls the damper actuator. The actuator’s angle of rotation is proportional to the length of time the signal is applied. A 24 Vac control signal to wires 1 and 6 (G-Y1) causes the actuator coupling to rotate clockwise.
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Mounting and Installation Technical Instructions Document No. 155-188P25 December 26, 2007 You must place the actuator on the damper shaft so that the front of the actuator is accessible. The label is on the front side. EA1002R1 The minimum damper drive shaft length is 3/4-inch (20 mm).
Technical Instructions Document No. 155-188P25 December 26, 2007 Wiring OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control All wiring must conform to NEC and local codes and regulations. Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers. The sum of the VA ratings of all actuators and all other components powered by one transformer must not exceed the rating of the transformer.
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Technical Instructions Document No. 155-188P25 December 26, 2007 Wiring , Continued Terminal Strip NOTE: Maximum wire size for the GDE131.1T 14 AWG. GDE161.1T CCW 7 CW 6 GDE131.1T M EA1094R1 CW CCW Figure 17. GDE131.1T Terminal Strip. Strain Relief 90 45 90 EA1091R1 Supply 24Vac 1 Supply Figure 18. GDE131.1T Wiring Diagram.
Technical Instructions Document No. 155-188P25 December 26, 2007 OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Wiring, Continued Post Header AMP GDE131.1N The GDE131.1N has two sets of identical contacts as shown in Figure 20. • All wiring must conform to NEC and local codes and regulations. • Use earth ground isolating step-down Class 2 transformers. Do not use autotransformers.
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Technical Instructions Document No. 155-188P25 December 26, 2007 Wiring, Continued Post Header AMP, Continued GDE131.1N Daisy Chain The input cable (purchased separately) brings power and a control signal to the first actuator in a daisy chain configuration. Table 3.
Technical Instructions Document No. 155-188P25 December 26, 2007 OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Wiring, Continued Table 4. Daisy Chain Cable GDE131.1N 12 ft 12 pk 25 ft 12 pk 985-134 Daisy Chain 985-135 90 90 45 90 45 45 90 90 90 EA1238R1 Input cable from controller sold separately Figure 23. WARNING: Do not daisy chain more than 12 actuators together at any time. Troubleshooting WARNING: Do not open the actuator.
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Technical Instructions Document No. 155-188P25 December 26, 2007 Wiring Designations Each wire has the standard symbol printed on it. CW SUPPLY CCW NEUT EARTH GROUND ISOLATING CLASS 2 TRANSFORMER FOR 24 Vac POWER 24 Vac EA1095R1 : SAFETY ISOLATING TRANSFORMER PER EN 60742 120 Vac Figure 24. Floating Control. Table 5. Floating Control 24 Vac.
Technical Instructions Document No. 155-188P25 December 26, 2007 Start-Up/ Commissioning OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control 1. Check that the wires are connected correctly. 2. Connect wires 1 (red) and 6 (violet) to a Digital Multimeter (DMM) with the dial set at Vac. Apply a control signal (24 Vac) to wires 1 and 6 to verify that the operating voltage is within range. 3. Connect wires 1 (red) and 7 (orange) to a DMM with the dial set at Vac.
OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Technical Instructions Document No. 155-188P25 December 26, 2007 Dimensions 7/16 (11) 90 min. 4 inch 100 mm 1/32 (0.8) 1/2 (12) 25/32 (20) 5-7/16 (137) min. 1/4 inch 6 mm min. 8 inch 200 mm 3-7/16 (87) 6-5/8 (168) 5/32 (4) 15/16 (94) min. 1 inch 25 mm EA0531R2 min. 2-3/8 inch 60 mm 2-3/8 (60) min. 3/8 inch 10 mm EA0530R3 13/16 (21) 2-3/4 (70) Figure 25.
Technical Instructions Document No. 155-188P25 December 26, 2007 OpenAir Non-Spring Return Rotary Electric Damper Actuator 24 Vac Floating Control Dimensions, Continued .46 (12) 90 min. 4 (100) .04 (1) 1/2 (12) 25/32 (20) 6.2 (156,3) min. .25 (6) min. 8 (200) 3.4 (87) 6-5/8 (168) .8 (19,3) .16 (4,15) .96 (24) EA0531R2 2.4 (61) min. 2.38 (60) 1.8 (44,9) EA1242R1 .84 (21,4) 2.8 (70,7) Figure 26. GDE131.1T, GDE131.1N, and Mounting Bracket Dimensions in Inches (Millimeters).