Data Sheet for Product
4 / 8
Siemens A6V10636280_en--_c
Building Technologies 2018-04-09
Engineering
Potentiometer and auxiliary switches
Potentiometer and auxiliary switches cannot be added in the field. For this reason, order the
type that includes the required options.
Installation
WARNING
No internal line protection for supply lines to external consumers
Risk of fire and injury due to short-circuits
● Adapt the line diameters as per local regulations to the rated value of the installed fuse.
Maintenance
The actuators GD..14..1E/RW are maintenance-free.
Disposal
The device is considered electrical and electronic equipment for dis-
posal in terms of the applicable European Directive and may not be
disposed of as domestic garbage.
∂ Dispose of the device through channels provided for this
purpose.
∂ Comply with all local and currently applicable laws and regu-
lations.
Technical data
Power supply GDD1..1E/RW GDA1..1E/RW
Operating voltage DC 24…45 V ⎓ +25 % / -30 % (16.8…56.3 V ⎓)
1)
Power consumption Running 1.5 W 1.0 W
Holding 0.5 W 0.5 W
Functional data GDD1..1E/RW GDA1..1E/RW
Nominal torque
Maximum torque (blocked)
5 Nm
7 Nm
Nominal rotary angle
Max. rotary angle
90°
95° ± 2°
Runtime for 90° rotary angle 30 s 90 s
Actuator sound power level 32 dB(A) 30 dB(A)
Feedback potentiometer
Change of resistance (wires P1-P2)
Load
GD..142.1E/RW (only):
0…5000 ς
<0,25 W
Auxiliary switches (GD..146.1E/RW only)
Contact rating
Switching voltage
Switching range for auxiliary switches
Setting increments
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V ⎓
0.8 A resistive, 0.5 A inductive, min. 10 mA @ DC 60 V ⎓
DC 12…60 V ⎓
5°…90°
5°
1)
C-UL: Permitted only to DC 30 V ⎓