User Manual
5
Siemens A6V11681606_en--_a
Smart Infrastructure 2020-06-09
Technical data
Power supply (G..D1…1E)
GDD1..1E
GLD1..1E
Operating voltage (SELV/PELV) / Frequency
AC 24 V ~ ± 20 % (19.2…28.8 V ~) / 50 / 60 Hz
DC 24…48 V ⎓ ± 20 % (19.2…57.6 V ⎓)
1)
Power consumption running
G..D14..1E,
G..D16..1E
1.5 W/2.8VA
1.7W/3.0VA
1.9 W/3.4VA
2.1 W/3.6VA
Power consumption holding
G..D14..1E,
G..D16..1E
0.5 W
0.7 W
0.5 W
0.7 W
Function data
GDD..1E
GLD..1E
Nominal torque
Maximum torque (blocked)
Minimum holding torque
5 Nm
10 Nm
5 Nm
8 Nm
16 Nm
8 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ± 2°
Runtime for 90° rotary angle
30 s
Actuator sound power level
32 dB (A)
Inputs
Positioning signal for GDD14..1E
Operating voltage
AC 24 V ~ / DC 24…48 V ⎓
(wires 1-6 / G-Y1)
(wires 1-7 / G-Y2)
clockwise
counterclockwise
Positioning signal for GDD16..1.E
Input voltage
Current consumption
Input resistance
Max. Permissible input voltage
Protected against faulty wiring
(wires 8-2 / Y-G0)
DC 0/2…10 V ⎓
0.1 mA
>100 k
DC 35 V ⎓ limited to DC 10 V ⎓
max. AC 24 V ~ / DC 24…48 V ⎓
Hysteresis for non-adjustable characteristic function
60 mV
Outputs
Position indicator
Output signal (GDD16..1E)
Output voltage U
Max. output current
Protected against faulty wiring
(wires 9-2 / U-G0)
DC 0…10 V ⎓
DC ±1 mA
Max. AC 24 V ~ / DC 24…48 V ⎓
Auxiliary switches (G..D146.1E only)
Switching voltage
Contact rating
AC 24…250 V ~ / DC 12…30 V ⎓
6 A resistive, 2 A inductive, min. 10 mA @ AC
4 A resistive, 2 A inductive, min. 10 mA @ DC 30 V ⎓
0.8 A res., 0.5 A inductive, min. 10 mA @ DC 60 V ⎓
Electric strength auxiliary switch against housing
Switching range for auxiliary switches / setting increments
Factory switch setting: Switch A
Switch B
AC 4 kV
5…90° / 5°
5°
85°
Connection cables
Cable length
0.9 m
Cross section of prewired connection cables
0.75 mm
2
Permissible length for signal lines
300 m
Degree of protection
Insulation class
AC 24 V ~ / DC 24…48 V ⎓
auxiliary switches
As per EN 60730
III
II
Housing protection
IP 54 as per EN 60529