Data Sheet for Product
8 / 14
Siemens A6V10636150_en--_f
Smart Infrastructure 2021-11-08
Technical data
Power supply GDB1..9E..
Operating voltage (SELV/PELV) /
Frequency
GDB141.9E
GDB161.9E
AC 24 V ~ ±20 % (19.2…28.8 V ~) / 50/60 Hz
DC 24…48 V
⎓
±20 % (19.2…57.6 V
⎓
)
1)
GDB161.9E/MO AC 24 V ~ ±20 % (19.2…28.8 V ~) / 50/60 Hz
DC 24…48 V
⎓
±20 % (19.2…28.8 V
⎓
)
Power consumption running GDB141.9E
GDB161.9E
GDB161.9E/MO
2 VA / 1 W
2.1 VA / 1.2 W
2.6 VA / 1.7 W
Power consumption holding GDB141.9E
GDB161.9E
GDB161.9E/MO
0.5 W
0.7 W
1.2 W
Power supply GDB341.9E
Operating voltage / Frequency AC 100…240 V ~ ±10 % (90…264 V ~) / 50/60 Hz
Power consumption running 5 VA / 1.6 W
Power consumption holding 0.9 W
Function data
Nominal torque
Maximum torque (blocked)
Minimum holding torque
5 Nm
10 Nm
5 Nm
Nominal rotary angle (with position indication)
Maximum rotary angle (mechanic limitation)
90°
95° ± 2°
Runtime for 90° rotary angle 150 s
Permissible medium temperature in the valve in combination
with GDB.. actuators
0…120 °C
Actuator sound power level 28 dB(A)
Inputs
Positioning signal for GDB141.9E
Operating voltage
AC 24 V ~ / DC 24…48 V
⎓
(wires 1-6/G-Y1)
(wires 1-7/G-Y2)
clockwise
counterclockwise
Positioning signal for GDB341.9E
Operating voltage
AC 100…240 V ~
(wires 4-6/N-Y1)
(wires 4-7/N-Y2)
clockwise
counterclockwise
Positioning signal for GDB161.9E..
Input voltage
Current consumption
Input resistance
(wires 8-2/Y-G0)
DC 0/2…10 V
⎓
0.1 mA
>100 k
Max. permissible input voltage
Protected against faulty wiring
Hysteresis
DC 35 V
⎓
limited to DC 10 V
⎓
max. AC 24 V ~ / DC 24…48 V
⎓
60 mV
Communication GDB161.9E/MO
Communication protocol
Modbus RTU RS-485, not galvanically isolated
Number of nodes Max. 32
Address range 1...248 / 255
Factory setting 255
Transmission formats 1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Factory setting 1-8-E-1
Baud rates (kbaud) Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 / 115.2
Factory setting Auto
Bus termination 120 Ω electronically switchable
Factory setting Off