Data Sheet for Product
    7 / 12 
CE1N3547en_e    Siemens 
2021-10-20    Smart Infrastructure 
KNX Group Objects 
Group Objects Table   
Nr. 
Name in ETS 
Object 
function  
Flags 
Data point type KNX 
Range 
C 
R 
W 
T 
U 
ID 
DPT_Name 
Format 
Unit 
1 
Fault information 
Transmit 
1 
1 
0 
1 
0 
219.001 
_AlarmInfo 
6 Byte 
--- 
cf. Description next page 
2 
Fault state 
Transmit 
1 
1 
0 
1 
0 
1.005 
_Alarm 
1 bit 
--- 
0 = No alarm 
1 = Alarm 
3 
Fault transmission 
Receive 
1 
0 
1 
0 
1 
1.003 
_Enable 
1 bit 
--- 
0 = Disable 
1 = Enable 
4 
Setpoint 
Receive 
1 
1 
1 
0 
1 
5.001 
_Scaling 
1 Byte 
% 
0…100% 
5 
Damper position 
Transmit 
1 
1 
0 
1 
0 
5.001 
_ Scaling 
1 Byte 
% 
0...100% 
6 
Volume flow 
relative
 1)
Transmit 
1 
1 
0 
1 
0 
5.001 
_ Scaling 
1 Byte 
% 
0...100% 
Transmit 
1 
1 
0 
1 
0 
8.010 
_Percent_V16 
2 Bytes 
% 
-327.68...327.67% 
Transmit 
1 
1 
0 
1 
0 
5.004 
_ Percent_U8 
1 Byte 
% 
0...255% 
7 
Volume flow 
absolute 
1)
Transmit 
1 
1 
0 
1 
0 
9.009 
_Value_Airflow 
2 Bytes 
m
3
/h 
-670 760...670 760 m3/h 
Transmit 
1 
1 
0 
1 
0 
14.077 
_ Volume_Flux 
4 Bytes 
m
3
/s 
0…(2
32 
-1) 
8 
Fault 
Transmit 
1 
1 
0 
1 
0 
1.005 
_Alarm 
1 bit 
--- 
0 = No alarm 
1 = Alarm 
9 
Overridden 
Transmit 
1 
1 
0 
1 
0 
1.002 
_Bool 
1 bit 
--- 
0 = False 
1 = True 
10 
Override position 1 
Receive 
1 
1 
1 
0 
1 
1.003 
_Enable 
1 bit 
--- 
0 = Disable 
1 = Enable 
11 
Override position 2 
Receive 
1 
1 
1 
0 
1 
1.003 
_Enable 
1 bit 
--- 
0 = Disable 
1 = Enable 
12 
Balancing mode 
Receive 
1 
1 
1 
0 
0 
1.003 
_Enable 
1 bit 
--- 
0 = Disable 
1 = Enable 
13 
Vmin 
Receive 
1 
1 
1 
0 
1 
8.010 
_Percent_V16 
2 Bytes 
% 
-327.68...327.67% 
14 
Vmax 
Receive 
1 
1 
1 
0 
1 
8.010 
_Percent_V16 
2 Bytes 
% 
-327.68...327.67% 
15 
Vnom 
Read-only 
1 
1 
0 
0 
0 
9.009 
_Value_Airflow 
2 Bytes 
m3/h 
-670 760...670 760 m3/h 
16 
Opening direction 
Read-only 
1 
1 
0 
0 
0 
1.012 
_Invert 
1 bit 
--- 
0 = Not Inverted 
1 = Inv. 
17 
Diff. pressure 
1)
Read-only 
1 
1 
0 
0 
0 
9.006 
_Value_Pres 
2 Bytes 
Pa 
0...670 760 Pa 
Read-only 
1 
1 
0 
0 
0 
14.058 
_Value_Pressure 
4 Bytes 
Pa 
0...(2
32 
-1) 
18 
Coefficient 
Read-only 
1 
1 
0 
0 
0 
14.* 
4-Byte Float 
4 Bytes 
--- 
0...3.16 
19 
OEM-Reset 
Receive 
1 
0 
1 
0 
0 
1.017 
_Trigger 
1 bit 
--- 
0, 1 = Trigger 
1)
 For some group objects,
alternative data point types (DPT) can be selected in ETS. The first entry indicates the default setting. 