Basic Documentation

39 / 42
Siemens VAV Compact Controller Modbus RTU A6V10631862_en--_e
Smart Infrastructure 2021-10-26
9.3.10 Reset behavior
The actuator supports the following re-initialization / reset behavior:
Local reset by push-button: cf. section 2.4.2
Tool-reset, cf. section 5.1.2
Remote reset: Using “RemoteFactoryReset” command.
Effect of reset:
Process values: set to ex-works default values.
Parameters:
- Application and actuator parameters are set to factory or OEM defaults,
- Network parameters are reset only in case of local reset, not by remote
reset (otherwise loss of communication).
Counters are not reset.
Status flags are not reset.
Device Information and Factory Data are not reset.
9.3.11 Self-test
The actuator supports a self-test. When triggered, the self-test runs the actuator to
the detected limits and sets the flags in register 769 according to the result (bit 09 =
1”failed” or bit 10 = 1 “passed”).
The self-test is not passed when the limits were not reached from the lower
end (results in jam).
If the limits can be exceeded, the self-test is not evaluated as failed.
9.3.12 Configuration check
The actuator supports a basic configuration check for the relation between Vmin
and Vmax: Vmax must be greater than Vmin, otherwise this is regarded an invalid
configuration. Tolerance level is 2% difference.
In case of an invalid configuration, the LED blinks red and the flag “invalid
configuration” in the status register (bit 11 in reg. 769) is set to “1”.
9.4 Object and function priorities
Prio
State
Behavior after power reset
1
Manual gear disengagement
Independent
2
Adaptation run
Will be restarted all over
1)
3
Self-test run (status)
Will be cancelled (reset)
1)
4
Local override control
Will be reset
5
Remote override control
Will be reset
6
Setpoint
Will be reset
7
Backup mode
Remains unchanged
1)
Will be overridden by Backup mode.