Data Sheet for Product

12
Siemens
CE1N3544en
Smart Infrastructure
2021-10-25
Tool =
Configuration and service interface
(from Series E: use 7-pin plug)
No.
Code
Color
Abbreviation
Meaning
Cable 1: black sheathing
1
G
Red
RD
System voltage AC 24 V
2
G0
Black
BK
System neutral AC 24 V
6
Y1
Purple
VT
Positioning signal "actuator's rotation direction" (G0 switched),
dependent on the rotation direction setting
7
Y2
Orange
OG
Positioning signal "actuator's rotation direction" (G0 switched),
dependent on the rotation direction setting
8
YC
Grey
GY
Air volume flow reference signal DC 0/2…10 V (setpoint) or
communication signal
9
U
Pink
PK
Air volume flow measuring signal DC 0/210 V (actual value)
For connections at the configuration and service interface, note that voltages > 10 V at YC
cannot be processed.
To ensure the functions at YC, only one cable may be connected at a time; either the cable
for the air volume flow reference signal DC 0/2…10 V (setpoint), or the cable for the com-
munication signal.